7.9 Zone Signal Output


Example of use in operation) While the actuator is moving a zone signal is output inside the zone enclosed by

distances of 40 mm and 120 mm from the home. (40 mm

 Zone signal output 

120 mm)

Method) Use the parameters “Zone boundary+” and “Zone boundary–” to set the zone in

which the zone signal is output, as shown below:

Parameter No. 1

Zone boundary+

120

Parameter No. 2

Zone boundary–

40



ERC controller


































P




L





C

[4] [2]



[1]




[7] [3]

[6] [5]

PIO

Signal name

Start

Command position 1

Command position 2

Command position 4

*Pause

Position complete

Home return completion


Zone

*Alarm

Category

Input








Output


Select/enter a desired command position.

Start input ON

Position complete output OFF

Start input OFF

Movement to the selected position
completes.

Position complete output ON

Movement to the selected position starts.

Actuator enters the zone. Zone output ON

Actuator exits the zone. Zone output
OFF

Reference flow

[1]


[2]




[3]

[4]

[5]

[6]

[7]