7.9 Zone Signal Output
Example of use in operation) While the actuator is moving a zone signal is output inside the zone enclosed by
distances of 40 mm and 120 mm from the home. (40 mm
Zone signal output
120 mm)
Method) Use the parameters “Zone boundary+” and “Zone boundary–” to set the zone in
which the zone signal is output, as shown below:
Parameter No. 1
Zone boundary+
120
Parameter No. 2
Zone boundary–
40
ERC controller
P
L
C
[4] [2]
[1]
[7] [3]
[6] [5]
PIO
Signal name
Start
Command position 1
Command position 2
Command position 4
*Pause
Position complete
Home return completion
Zone
*Alarm
Category
Input
Output
Select/enter a desired command position.
Start input ON
Position complete output OFF
Start input OFF
Movement to the selected position
completes.
Position complete output ON
Movement to the selected position starts.
Actuator enters the zone. Zone output ON
Actuator exits the zone. Zone output
OFF
Reference flow
[1]
[2]
[3]
[4]
[5]
[6]
[7]