IMPORTANT APPLICATION INFORMATION

4.1

Motor with External Fan Cooling – Most totally enclosed fan-cooled (TEFC) and open

ventilated 3-phase AC induction motors will overheat if used beyond a limited speed range at

full torque. Therefore, it is necessary to reduce motor load as speed is decreased.

Note: Some fan-cooled motors can be used over a wider speed range. Consult the motor

manufacturer for details.

WARNING! Some motors have low speed characteristics which cause overheating and

winding failure under light load or no load conditions. If the motor is operated in this

manner for an extended period of time, it is recommended that the unloaded motor current be

checked from 2–15 Hz (60 – 450 RPM) to ensure motor current does not exceed the name-

plate rating. Do not use motor if the motor current exceeds the nameplate rating.