For 120 Hz output with

60 Hz motor, be sure

Jumper J1 is set to the

“60Hz” position and set

Jumper J2 to the “X2”

position. For 100 Hz

output with 50 Hz

motor, set Jumper J1 to

the “50Hz” position and

set Jumper J2 to the

“X2” position. See

Figure 12.

6.3

Automatic Start (CON1) –

The drive is factory set for

Automatic Start (jumper

installed onto CON1), as

shown in Figure 13, on page

27. CON1 is located on the

lower PC board. The drive will

automatically start when power

is applied and a run command is

given. The drive will automatical-

ly restart after a recovered fault

due to undervoltage, overvolt-

age, or short circuit.

26

FIGURE 12 – 120 Hz & 100 Hz

DRIVE OUTPUT FREQUENCY SELECTION

120 Hz Output with 60 Hz Motor

(J1 Installed in “60Hz” Position)

(J2 Installed in “X2” Position)

100 Hz Output with 50 Hz Motor

(J1 Installed in “50Hz” Position)

(J2 Installed in “X2” Position)

J2

J1

50/60Hz

X1 X2

J2

J1

50/60Hz

X1 X2

50/60

Output Frequency (Hz)

%

T

or

qu

e

0

0

2

50

100

100/120

FIGURE 11 – AVAILABLE TORQUE vs. OUTPUT FREQUENCY