KB Electronics KBVF-23P User Manual

Page 7

Advertising
background image

1.2

Ground Connection – Connect the ground wire (earth) to the ground screw, as shown in

Figure 16, on page 31. See Section 9.2, on page 31.

Note: Model KBVF-21D, due to its double insulated design, does not contain a ground screw.

1.3

AC Line Fusing – It is recommended that a fuse(s) or circuit breaker be installed in the AC

line. Fuse each conductor that is not at ground potential. For the recommended fuse size, see

Table 1, on page 14. Also see Section 10, on page 35.

1.4

Motor Connection – Wire the motor to quick-connect Terminals “U”, “V”, “W”, as shown in

Figure 16, on page 31. (Special reactors may be required for cable lengths over 100 ft. (30 m)

– consult our Sales Department.) See Section 9.3, on page 31.

Note: The drive is programmed to operate 3-phase AC induction motors. For PSC motors,

optional software is required – contact our Sales Department.

1.5

60 Hz and 50 Hz Motor Operation (Jumpers J1 and J2 On the Lower PC Board) – The

drive is factory set for 60 Hz motor operation (Jumper J1 set to the “60Hz” position and

Jumper J2 set to the “X1” position). For 50 Hz motor operation, set Jumper J1 to the “50Hz”

position and be sure Jumper J2 is set to the “X1” position. See Section 6.2.1, on page 25.

1.6

Trimpot Settings – All trimpots have been factory set for most applications, as shown in

Figure 4, on page 20. Some applications require adjustment of the trimpots in order to tailor

the drive for a specific requirement. See Section 13, on page 38.

1.7

Main Speed Potentiometer Connection – For unidirectional speed operation, wire the 5 kΩ

potentiometer (supplied) to Terminals “P1” (low), “P2” (wiper), “P3” (high). See Section 9.4,

on page 31.

7

Advertising
This manual is related to the following products: