1.8

Voltage Following – An isolated* 0 – 5 Volt DC analog signal input can be used to control

motor speed in lieu of the Main Speed Potentiometer. The drive output will linearly follow the

analog signal input. Connect the signal input positive lead (+) to Terminal “P2” and the nega-

tive lead (–) to Terminal “P1”. See Section 9.5, on page 32.

*If a non-isolated signal is used, install the SIVFR — Signal Isolator (Part No. 9597). The SIVFR

accepts voltage (0 to ±2.5 thru 0 to ±25 Volts DC) or current (4 – 20 mA DC) signal inputs.

See Section 3.5, on page 13.

Note: For signal following operation, the Minimum Speed Trimpot (MIN) must be set fully

counterclockwise.

WARNING! The signal input must be isolated from the AC line. Earth grounding

signal wiring will damage the drive and void the warranty. It is recommended that

the SIVFR — Signal Isolator and Run/Fault Relay (Part No. 9597) be installed when

using signal following.

2

SAFETY WARNING

Definition of Safety Warning Symbols

Electrical Hazard Warning Symbol – Failure to observe this warning could result in electrical

shock or electrocution.

Operational Hazard Warning Symbol – Failure to observe this warning could result in

serious injury or death.