WARNING! The signal input must be isolated from the AC line. Earth grounding

signal wiring will damage the drive and void the warranty. It is recommended that

the SIVFR — Signal Isolator and Run/Fault Relay (Part No. 9597) be installed when

using signal following.

9.6

Manual Start Switch Connection

(CON1) – The Manual Start Mode is

used to manually start the drive or

restart the drive (reset) if a fault has

occurred. To operate the drive in

the Manual Start Mode, remove the

factory installed jumper on CON1

and install the 2-wire connector

(supplied). CON1 is located on the

lower PC board. The connector

must be wired to a momentary

switch or contact, as shown in

Figure 19.

In the Manual Start Mode, the drive will trip due to all faults (Overvoltage, Undervoltage, Short

Circuit, and I

2

t) and remain tripped even when the fault is cleared. To Start/Reset the drive, the

switch or contact must be manually closed. Also, the drive must be restarted each time the

AC line is interrupted.

For Automatic Start, see Section 6.3, on page 26.

Notes: 1. See Section 11.2, on page 35. Also see Section 12.2, on page 38. 2. The drive can

be factory programmed for Run/Stop operation with momentary contacts.

33

FIGURE 19 – MANUAL START SWITCH CONNECTION

Jumper Removed

Connector Installed for

Manual Start Switch

CON1

A/M

Manual Start Switch

(Momentary Contacts)

(Push to Run)

White

Black

CON1