WARNING! Do not earth

ground any Main Speed

Potentiometer terminals.

Note: When mounting the Main Speed

Potentiometer, be sure to install the insulat-

ing disc (supplied) between the poten-

tiometer and the panel.

9.5

Voltage Following Connection – An iso-

lated* 0 – 5 Volt DC analog signal input can

be used to control motor speed in lieu of

the Main Speed Potentiometer. The drive

output will linearly follow the analog signal

input. Connect the signal input positive lead

(+) to Terminal “P2” and the negative lead

(–) to Terminal “P1”. The terminals are locat-

ed on the lower PC board. With external

circuitry, a 0 – 10 Volt DC analog signal can

also be used. See Figure 18.

*If a non-isolated signal is used, install the

SIVFR — Signal Isolator (Part No. 9597).

The SIVFR accepts voltage (0 to ±2.5 thru

0 to ±25 Volts DC) or current (4 – 20 mA

DC) signal inputs. See Section 3.5, on page 13.

Note: For signal following operation, the Minimum Speed Trimpot (MIN) must be set fully

counterclockwise.

32

FIGURE 18 – VOLTAGE FOLLOWING CONNECTION

0 – 5 Volts DC (Isolated)

0 – 10 Volts DC (Isolated)

P1

P2

P3

0 - 5

Volts DC

+

-

V

P1

P2

P3

0 - 10

Volts DC

V

+

-

10k

10k

Wiper

Low

High

P1

(Supplied) (Front View)

Main Speed Potentiometer

P3

P2

FIGURE 17 – MAIN SPEED

POTENTIOMETER CONNECTION