KB Electronics KBDF-48 User Manual

Page 26

Advertising
background image

26

TABLE 7

DRIVE INPUT AND OUTPUT CONNECTIONS

1

Terminal Blocks

No.

Description

Specifications

1

Power Supply

–5 Volts DC at 1 mA Max.

2

Power Supply

+5 Volts DC at 1 mA Max.

3 Analog Signal Input

0 – ±5 / ±10 Volts DC,

0 – 20 / 4 – 20 mA DC

4

Common

2

──

5 MFIT

1

6 MFIT

2

7 MFIT

3

8 MFIT

4

9 MFIT

5

N.O. Contacts or NPN / PNP Transistors

7 Preset Frequencies,

Up Frequency Command,

Down Frequency Command,

Accel/Decel #2,

Forward/Stop Command,
Reverse/Stop Command,

External Fault (N.O. Contact), Reset, N.O.

Start (2-Wire or 3-Wire Start/Stop), N.C.

Stop (3-Wire Start/Stop),

External Fault (N.C. Contact)

10

External

Power Supply Input

5 – 24 Volts DC Input

11

Common

2

──

TB1

on Drive

3

1 2

4 5 6

8

7

9

11

10

12

12

Analog Output

0 – 5 Volts DC

13

Open Collector

Output

NPN

14 MFIT

6

15 MFIT

7

Same As

MFIT 1 – MFIT 5 Above

16

Common

2

──

17

Power Supply

+5 Volts DC at 1 mA Max.

18

Analog Input #2

0 – 2.5 thru 0 – 25 Volts DC

TB1

on IODF

19

Common

2

──

N.O. Normally

Open

COM Relay

Common

3

TB2

on Drive

TB3

on IODF

N.C. Normally

Closed

Run, Fault,

Target Frequency (5.03 ± 5.04),

Frequency Threshold Level (> 5.03 –5.04),
Frequency Threshold Level (< 5.03 +5.04),

I

2

t or I•t Fault, Load Loss (See 5.05),

External Fault

Notes: 1. For additional inputs and outputs, install the optional IODF Input/output Multi-Function
Expansion Module (Part No. 9646). See Appendix A, on page 64. 2. Common Terminals "4",
"11", "16", and "19" are internally wired together. 3. Relay Commons are not internally wired to
Common Terminals "4", "11", "16", and "19".

Advertising