Function Group 0: Motor and Drive Parameters

Function

No. Description

Range/Code

Factory

Setting

User

Setting

0.00 * Rated Motor Frequency (Hz)

0000: 60 Hz
0001: 50 Hz
0002: Special (Set by 0.05)

0000

0.01 * Motor Nameplate Current (Amps)

(1)

0.02 * Reserved

0.03 * Torque

Mode

0000: Constant Torque (Machinery)
0001: Variable Torque (HVAC)

0000

0.04 * GFCI

Operation

(2)

0000: GFCI Operation Disabled
0001: Operation with Standard GFCI
0002: Operation with Sensitive GFCI

0000

0.05 * Motor Nameplate Frequency (Hz)

(3, 4)

30 – 240 60,

50

0.06 *

Motor Nameplate Voltage
(% Drive Output)

(5)

0 – 100

100

(6)

Notes: (1) Factory Setting is the drive rated output current. This function is used to enter the
Motor Nameplate Rated Current, which allows proper operation of the I

2

t Motor Overload

Protection. (2) GFCI operation overrides the Switching Frequency set by Function 3.15.
(3) When the drive is set for 50 Hz motors (Function 0.00 set to code "0001"), the Motor
Frequency factory setting will automatically reset to 50 Hz. (4) The Motor Frequency for
standard 50 Hz or 60 Hz motors is set by Function 0.00. For custom motors (e.g., 100 Hz) set
Function 0.00 to code "0002" and Function 0.05 to the Motor Nameplate Rated Frequency.
(5) This function is used for motors with non-standard nameplate rated voltage (e.g., 80 Volts
AC). (6) The factory set output of the drive is 100% of the AC Line input voltage. In 60 Hz Mode
(Function 0.00 set to code "0000") the drive output will be 230 Volts, maximum, for 230 Volt
motors. In 50 Hz Mode (Function 0.00 set to code "0001") the drive output will be 220 Volts,
maximum, for 220 Volt motors.
*Functions which can only be changed while the drive is in the Stop Mode.