56

Function Group 1: Run/Stop Mode

Function

No. Description

Range/Code

Factory

Setting

User

Setting

1.00 * Run/Stop-Forward/Reverse

Control

(1)

0000: Keypad
0001: External Contacts

0002: Communication

(2)

0001

1.01 * Forward/Reverse

Control

0000: Instant Reverse
0001: Stop Command Must be Given
Prior

to

Reverse

Command

0002: Reverse Command Disabled
0003: Forward Command Disabled

0000

1.02 * Motor

Direction

0000: Forward
0001: Reverse

0000

1.03 * Start

Command

0000: Accelerates to Last Set
Frequency
0001: Accelerates to Lower
Frequency Limit (See 3.01)

0000

1.04 * Restart

Mode

0000: Spin Start
0001: Stop before Restart

0000

1.05 * Auto/Manual

Start

Mode

0000: Manual Start Mode
0001: Manual Start with Ride-Through
(Set

by

1.06)

0002: Auto Start After Undervoltage
Fault

Clears

0003: Auto Start All Faults
(Except

I

2

t, I•t, and Short Circuit

Faults)
0004: Auto Start All Faults
(Except Short Circuit Fault)

(3)

0000

1.06 * Ride-Through Time (Seconds)

0.0 – 2.0

0.5

1.07 * Number of Restart Attempts

0 – 10

3

1.08 * Start Delay Time (Seconds)

0 – 240

0

1.09 * Stop

Mode

0000: Regenerate-to-Stop
0001: Coast-to-Stop
0002: Regeneration with Injection
Brake-to-Stop

(Set by 1.11 – 1.13)

0000

1.10 * Holding Torque in Stop Mode (%)

0 – 10

0

1.11

Injection Brake Start Frequency (Hz) 0.00 – 240.0

0.00

1.12

Injection Brake Level (%)

0 – 30

0

1.13

Injection Brake Time (Seconds)

0.0 – 25.5

0.0

Notes: (1) Sets the source for the Run/Stop-Fwd/Rev in Remote mode (see Function 2.03).
(2) DIDF Option Board required. (3) For Auto Start, Function 1.07 must be set to greater than "0"
(factory setting is "3").
*Functions which can only be changed while the drive is in the Stop Mode.