KB Electronics KBDF-48 User Manual

Page 60

Advertising
background image

60

Function Group 7: Multi-Function Input Terminals

Function

No. Description

Range/Code

Factory

Setting

User

Setting

7.00 * Multi-Function Input 1 (Terminal 5)

(1)

0000

7.01 * Multi-Function Input 2 (Terminal 6)

(1)

0001

7.02 * Multi-Function Input 3 (Terminal 7)

(1)

0002

7.03 * Multi-Function Input 4 (Terminal 8)

(1)

0009

7.04 * Multi-Function Input 5 (Terminal 9)

(1)

0010

7.05 *

Multi-Function Input 6 (Terminal 14)

(1, 4)

0003

7.06 *

Multi-Function Input 7 (Terminal 15)

(1, 4)

0000: Preset Frequency Operation

(2)

0001: Preset Frequency Operation

(2)

0002: Preset Frequency Operation

(2)

0003: Up Frequency Command
(See

7.14)

0004: Down Frequency Command
(See

7.14)

0005: Accel/Decel #2 (See 7.16)
0006: Forward/Stop Command
0007: Reverse/Stop Command
0008: External Fault (N.O. Contact)
0009: Reset
0010: N.O. Start
(2-Wire or 3-Wire Start/Stop)
0011: N.C. Stop (3-Wire Start/Stop)
0012: External Fault (N.C. Contact)

0004

7.07

Preset Frequency 1 (Hz)

0.00 – 240.0

10.00

7.08

Preset Frequency 2 (Hz)

0.00 – 240.0

15.00

7.09

Preset Frequency 3 (Hz)

0.00 – 240.0

20.00

7.10

Preset Frequency 4 (Hz)

0.00 – 240.0

25.00

7.11

Preset Frequency 5 (Hz)

0.00 – 240.0

30.00

7.12

Preset Frequency 6 (Hz)

0.00 – 240.0

35.00

7.13

Preset Frequency 7 (Hz)

0.00 – 240.0

40.00

7.14

Up/Down Frequency Control Mode

0000: Free-Running

(3)

0001: Incremental Change (See 7.15)

0000

7.15

Increment of Up/Down Frequency (Hz) 0.01 – 30.00

1.00

7.16

Accel/Decel #2 Time (Seconds)

0.3 – 180.0

10.0

7.17–7.33 Reserved

— —

Note: (1) Each of the 7 Multi-Function Inputs can be programmed for any of the respective
function codes ("0000" – "0012"). (2) Preset Frequencies 1 – 7 are obtained by selecting a
specific combination of 3 Multi-Function Input Terminals. The specific frequencies are
programmed in Functions 7.07 – 7.13. (3) The rate of change of the "UP" Control for frequency
setting, using external contacts, is proportional to the Accel Time setting (Function 3.03). The
incremental rate of change of the "DOWN" Control for frequency setting, using external
contacts, is proportional to the Decel Time Setting (Function 3.04). (4) IODF Option Board
required.
*Functions which can only be changed while the drive is in the Stop Mode.


Function Group 8: PID (IODF Option Board Required)

Function

No. Description

Range/Code

Factory

Setting

User

Setting

8.00–8.10 Reserved

— —


Advertising
This manual is related to the following products: