JMP504 Input Type

Jumper pins 1 & 2 for Voltage follower or speed pot mode.

Jumper pins 2 & 3 for Current follower.

JMP505 Input Range Settings

Set jumper in position 1 for 0-5 VDC signal or speed pot input.

Set jumper in position 2 for 0-10 VDC signal.

Set jumper in position 3 for 4-20 mA signal. *

* The 4-20 mA ZERO SET potentiometer should be used

to calibrate the zero (or minimum) speed of the drive with

4mA applied to the input. For voltage inputs this pot

should be set to full CCW.

Figure 12. Jumper Settings--JMP504 and JMP505

JMP504

JMP504

JMP505

1 & 2 for Voltage or speed pot input

2 & 3 for Current

1 = 0 - 5 VDC or speed pot INPUT

2 = 0 - 10 VDC

3 = 4 - 20 mA

1 2 3

1 2 3

JMP505