LEESON SM Series Sub-Micro Inverters User Manual

Page 20

Advertising
background image

16

11.0

SM Series

CONTROL WIRING DIAGRAMS

11.1

SM Series

TERMINAL STRIP

Shown below is the control terminal strip, along with a brief description of the function of each terminal.
The following wiring diagram examples provide a quick reference to wire the drive for the most common
configurations.

NOTE: The function of terminals TB-13A, TB-13B, TB-13E and the Form A relay at terminals
16 and 17 are dependent on the programming of certain parameters. Refer to Section 15.0 -
DESCRIPTION OF PARAMETERS.

The digital inputs (terminals 1, 13A, 13B, and 13E) are active-high. They can be activated using
terminal 11 (which is +12 VDC) as shown in the following diagrams, or by using an external
voltage source with a range of +12 VDC to +28 VDC (± 10%).

1

2

5

6

11

13A

13B

13E

25

16

17

MAINTAINED

RUN/STOP

CONTACT

FORM A

RELAY

RUN

SIGNAL COMMON

0-10 VDC INPUT

SPEED POT POWER SUPPL

Y

DIGIT

AL INPUT REFERENCE

TB-13A FUNCTION SELECT

TB-13B FUNCTION SELECT

TB-13E FUNCTION SELECT

4-20 mA INPUT