LEESON SM Series Sub-Micro Inverters User Manual

Page 38

Advertising
background image

13

REMOTE KEYPAD: When the Remote Keypad option is being used, TB-13B must be set to
this function. Also, TB-13E (Parameter 12) must be set for REMOTE KEYPAD (21), and
CONTROL (Parameter 14) must be set to REMOTE KEYPAD ONLY (02).

NOTE: If the drive is commanded to JOG when running, the drive will enter JOG mode and run
at PRESET SPEED #2 (Parameter 32). When the JOG command is removed, the drive will STOP.

P12

TB-13E FUNCTION SELECT

This selects the function of terminal TB-13E. This terminal can be configured as a digital input (settings
01 to 10) or a digital status output (settings 11 to 20). When used as an input, closing TB-13E to
TB-11 (or opening in the case of settings 07 and 09) activates the selected function.

When used as an output, it can provide the drive’s status for monitoring. If the Remote Keypad option
is being used, this parameter must be set to REMOTE KEYPAD (21).

The following input functions can be selected:

01

NONE: Disables the TB-13E function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #3: Selects PRESET SPEED #3 as the AUTO speed reference. The drive will
operate at the frequency programmed into Parameter 33.

05

INCREASE FREQ: Closing TB-13E to TB-11 will increase the speed setpoint until the contact
is opened. INCREASE FREQ will only work when the drive is running. TB-13B must be
programmed for DECREASE FREQ.

06

START FORWARD: Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB-13E
to TB-11 to start the drive, and momentarily open TB-1 to TB-11 to stop.

07

EXTERNAL FAULT: Sets TB-13E as a normally closed external fault input. Open TB-13E to
TB-11 to trip the drive

08

INVERSE EXTERNAL FAULT: Sets TB-13E as a normally open external fault input. Close
TB-13E to TB-11 to trip the drive.

09

AUXILIARY STOP: When TB-13E is opened with respect to TB-11, the drive will decelerate
to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2
(Parameter 42).

10

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into
ACCEL/DECEL #2 (Parameter 42).

34