LEESON SM Series Sub-Micro Inverters User Manual

Page 36

Advertising
background image

32

09

AUTOMATIC SPEED MODE: Closes if an AUTOMATIC (terminal strip) speed reference is
active. Opens if a STANDARD (Parameter 5) speed reference is active.

10

REVERSE: Closes when reverse rotation is active. Opens when forward rotation is active. (see
Parameter 17 - ROTATION DIRECTION).

P10

TB-13A FUNCTION SELECT

This selects the function of terminal TB-13A. Closing TB-13A to TB-11 (or opening in the case of
settings 08 and 10) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13A function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #1: Selects PRESET SPEED #1 as the AUTO speed reference. The drive will
operate at the frequency programmed into Parameter 31.

05

START FORWARD. Sets up the drive for a 3-wire start/stop circuit. Momentarily close TB-13A
to TB-11 to START the drive, and momentarily open TB-1 to TB-11 to STOP.

06

RUN REVERSE: Close TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.
Close TB-1 to TB-11 to RUN in FORWARD DIRECTION and open to STOP.

07

START REVERSE: Momentarily close TB-13A to TB-11 to START the drive in the reverse
direction and momentarily open TB-1 to TB-11 to STOP. Parameter 17 - ROTATION must be
set to FORWARD AND REVERSE (02), and TB-13E must be used for START FORWARD.

08

EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. Open TB-13A to
TB-11 to trip the drive.

09

INVERSE EXTERNAL FAULT: Sets TB-13A as a normally open external fault input. Close
TB-13A to TB-11 to trip the drive.

10

AUXILIARY STOP: When TB-13A is opened with respect to TB-11, the drive will decelerate
to a STOP (even if STOP METHOD is set to COAST) at the rate set into ACCEL/DECEL #2
(Parameter 42).

11

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into
ACCEL/DECEL #2 (Parameter 42).

Advertising