DESCRIPTION OF PARAMETERS

P01

LINE VOLTAGE SELECTION

This calibrates the drive for the actual applied input voltage. Set this parameter to HIGH (01) for 120,
220-240, and 460-480 Vac input, or LOW (02) for 200-208 and 380-415 Vac input.

NOTE: If this parameter is changed while the drive is running, the new value will not take effect
until the drive is stopped.

P02

CARRIER FREQUENCY

This sets the switching rate of the output IGBT’s. Increasing the carrier frequency will result in less
audible motor noise. Available settings are: 4 kHz, 6 kHz, 8 kHz, and 10 kHz.

PARAMETER

CARRIER

AMBIENT OR OUTPUT

SETTING

FREQUENCY

DERATE (NOTE 2)

01

4 kHz

40 C or 100 %

02

6 kHz

40 C or 100 %

03

8 kHz

40 C or 100 %

04

10 kHz

35 C or 92 %

NOTES:

1.

The SM Series

drive is fully rated up to 8 kHz carrier frequency. If the 10 kHz carrier

frequency is selected, the drive’s ambient temperature rating OR output current rating must
be derated to the value shown in the table above.

2.

If this parameter is changed while the drive is running, the change will not take effect until
the drive is stopped.

P03

START METHOD

Automatic starting of equipment may cause damage to equipment and / or injury
to personnel! Automatic start should only be used on equipment that is
inaccessible to personnel.

01

NORMAL: The drive will start when the appropriate contact is closed on the terminal strip. See
Section 11 for possible control configurations.

02

START ON POWER UP: The drive will automatically start upon application of input power.

DANGER