11.2

TWO-WIRE START/STOP CONTROL

NOTES:

1.

Close TB-1 to TB-11 to RUN and open to STOP. TB-1 functions as a RUN input for
two-wire start/stop circuits, and a STOP input for three-wire start/stop circuits. Refer to
Section 11.3.

2.

If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) to RUN REVERSE (06). Close
TB-13A to TB-11 to RUN in the reverse direction, and open to STOP.

3.

For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE (Parameter
05) to 0-10 VDC (03) or 4-20 mA (04).

1

2

5

6

11

13A

13B

13E

25

16

17

MAINTAINED

RUN/STOP CONTACT

(FORWARD)

MAINTAINED

RUN/STOP CONTACT

(REVERSE)

FORM A

RELAY

RUN

SIGNAL COMMON

0-10 VDC INPUT

SPEED POT POWER SUPPL

Y

DIGIT

AL INPUT REFERENCE

TB-13A FUNCTION SELECT

(RUN REVERSE)

TB-13B FUNCTION SELECT

TB-13E FUNCTION SELECT

4-20 mA INPUT

17