18

11.3

THREE-WIRE START/STOP CONTROL

NOTES:

1.

Program TB-13E (Parameter 12) for START FORWARD (06).

2.

If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND
REVERSE (02), and program TB-13A (Parameter 10) for START REVERSE (07).

3.

Momentarily close TB-13E to TB-11 to START in the forward direction, or close TB-13A to
TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the
drive.

4.

For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE (Parameter
05) to 0-10 VDC (03) or 4-20 mA (04).

1

2

5

6

11

13A

13B

13E

25

16

17

MOMENTARY

STOP CONTACT

MOMENTARY

START CONTACT

REV

FWD

FORM A

RELAY

STOP

SIGNAL COMMON

0-10 VDC INPUT

SPEED POT POWER SUPPL

Y

DIGIT

AL INPUT REFERENCE

TB-13A FUNCTION SELECT

(ST

AR

T REVERSE)

TB-13B FUNCTION SELECT

TB-13E FUNCTION SELECT

(ST

AR

T FOR

W

ARD)

4-20 mA INPUT