The Analog_Out_205x driver supports the outputs on the PPC-205x
series Analog Output modules.
To associate a variable with an analog output:
1.
Open the Add Program/Resource Variable dialog box.
2.
Enter a unique variable Name.
3.
Select INT from the Type list.
4.
Select Output by clicking the check box.
5.
Select Analog_Out_205x from the IO Driver list.
6.
Select WORD from the IO Size list.
7.
Enter the IO Physical Address. The address is:
X.Z
X is the module address (31-34)
Z is the module I/O number (1-8)
8.
Click
[OK]
.
PPC-205x Analog Out Addressing Example
To create a variable named VoltsOut_2 that sets the level of the
second output on a PPC-205x module with its rotary address switch
set to 31, set the options in the Add Program/Resource Variable
dialog box as illustrated below.