W i r i n g

Wa t l o w S e r i e s 9 6

Output 1 Wiring

Figure 3.4a –

AC Outputs

•Electromechanical relay without
contact suppression

96 _ _ - D _ _ _ - _ _ _ _

Form C, 2 amps, off-state
impedance: 31M

•Solid-state relay without contact
suppression

96 _ _ - K _ _ _ - _ _ _ _

0.5 amps, off-state impedance:
31M

Figure 3.4b –

Switched DC, Open Collector

96 _ _ - C _ _ _ - _ _ _ _

•Switched dc
configuration

Supply current limited
to 30mA

•Open collector configuration

Maximum voltage 42VÎ (dc)

Maximum current 200mA

Figure 3.4c –

0-20mA and 4-20mA Process

96 _ _ - F _ _ _ - _ _ _ _

Maximum load impedance: 800

Figure 3.4d –

0-5VÎ, 1-5VÎ and 0-10VÎ (dc) Process

96-_ _ -F_ _ _ - _ _ _ _

Minimum load impedance: 1k

10

8

1

2

3

13 14 15

9

15

14

-

+

10

8

1

2

3

13 14 15

9

13 14

-

+

+V

Î

(dc)

Internal Circuitry

15

13

14

22 to 28V

Î

(dc)

10

8

1

2

3

13 14 15

9

External
Load

13

15

14

COM.

-

+

10

8

1

2

3

13 14 15

9

External

Load

15

14

COM. N.O.

L2

L1

(13 used for
D outputs only)

13

N.C.

customer-supplied

Quencharc

NOTE:

Successful installation
requires five steps:

• Choose the controller’s

hardware configuration
and model number
(Appendix);

• Choose a sensor

(Chapters Three and
Six, and Appendix);

• Install the controller

(Chapter Two);

• Wire the controller

(Chapter Three) and

• Configure the controller

(Chapters Four, Five
and Six).

NOTE:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of
an R.C. suppressor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.