Output 3 Wiring

Figure 3.6 –

AC Outputs

Electromechanical relay without contact suppression

96 _ _ - _ _ D_ - _ _ _ _

Form C, 2 amps, off-state impedance: 31M

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

External

Load

L2

L1

11

10

N.C.

N.O.

12

COM.

customer-supplied

Quencharc

NOTE:

Successful installation
requires five steps:

• Choose the controller’s

hardware configuration
and model number
(Appendix);

• Choose a sensor

(Chapters Three and
Six, and Appendix);

• Install the controller

(Chapter Two);

• Wire the controller

(Chapter Three) and

• Configure the controller

(Chapters Four, Five
and Six).

NOTE:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of
an R.C. suppressor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.

ç

WARNING:

To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.