Wa t l o w S e r i e s 9 6

W i r i n g

3 . 5

Output 2 Wiring

Figure 3.5a –

AC Outputs

•Electromechanical relay without contact suppression

96 _ _ - _ D _ _ _ - _ _ _ _

Form C, 2 amps,
off-state impedance:
31M

•Solid-state relay
without contact
suppression

96 _ _ - _ K _ _ - _ _ _ _

0.5 amps, off-state
impedance: 31M

Figure 3.5b –

Switched DC, Open Collector

96 _ _ - _ C _ _ - _ _ _ _

Open Collector

Max. voltage: 42VÎ (dc)

Max. current: 200mA

Switched DC

Max. dc supply current:
30mA

Supply voltage: 22 to 28VÎ (dc)

Figure 3.5c –

0-20mA and 4-20mA Process

96 _ _ - _ F _ _ - _ _ _ _

Maximum load
impedance: 800

Figure 3.5d –

0-5VÎ, 1-5VÎ and 0-10VÎ (dc) Process

96 _ _ - _ F _ _ - _ _ _ _

Minimum load
impedance: 1k

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

16 17

-

+

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

17 18

-

+

+V

Î

(dc)

Internal Circuitry

16

18

17

22 to 28V

Î

(dc)

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

+ 16 17 18 -

External
Load

COM.

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

External

Load

COM. N.C.

L2

L1

16 17 18

(18 used for

D outputs only)

N.O.

customer-supplied

Quencharc

NOTE:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of
an R.C. suppressor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.

ç

WARNING:

To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.

Advertising