Output 4 wiring, Output 4, Ac outputs – Watlow Series 96 User Manual

Page 13: Communications and retransmit option, Figure 3.7a, Figure 3.7b

Advertising
background image

Wa t l o w S e r i e s 9 6

W i r i n g

3 . 7

Output 4 Wiring

Figure 3.7a –

AC Outputs

Electromechanical relay without contact suppression

96 _ _ - _ _ _ D - _ _ _ _

Form C, 2 amps, off-state impedance: 31M

Figure 3.7b –

Communications and Retransmit Option

EIA/TIA-232

EIA/TIA-485

Retransmit Option

96 _ _ - _ _ _ R - _ _ _ _

96 _ _ - _ _ _ U - _ _ _ _

96_ _ - _ _ _ M - _ _ _ _

10

2

3

4

5

6

7

11

12

16 17 18

19 20 21

9

10

2

3

4

5

6

7

11

12

16 17 18

19 20 21

9

EIA/TIA-232
DB-25 Pinout
2

transmit

3

receive

4

RTS

5

CTS

6

DSR

7

common

8

DCD

12 DTR

EIA/TIA-232
DB-9 Pinout
1

DCD

2

receive

3

transmit

4

DTR

5

common

6

DSR

7

RTS

8

CTS

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

19 20 21

V out COM. I out

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

19 20 21

T-/R- COM. T+/R+

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

19 20 21

T out COM. R in

10

8

1

2

3

4

5

6

7

13 14 15

11

12

16 17 18

19 20 21

9

External

Load

COM. N.C.

L2

L1

19 20 21

N.O.

customer-supplied

Quencharc

NOTE:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, switched dc or
solid-state relay output
options requires use of
an R.C. suppressor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW
Paktron. Watlow Part No.
0804-0147-0000.

ç

WARNING:

To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to install
and operate the Series
96. Failure to do so could
result in injury or death.

V out: 1,000

minimum

load impedance.

I out:

800

maximum

load impedance.