Specifications, Product specifications . . . . . . . . . . . a.5 – Watlow Series 96 User Manual

Page 64

Advertising
background image

A . 5

A p p e n d i x

Wa t l o w S e r i e s 9 6

Output Types
Open Collector/Switched DC

• Open collector configuration:

Maximum voltage 42V

Î

(dc)

Maximum current 200mA
Maximum “on” resistance 1.1

Maximum offstate leakage current 100µA

• Switched dc configuration:

Switched dc supply voltage 22 to 28V

Î

(dc)

dc supply current limited to 30mA

Solid-state Relay

• Optically isolated
• Zero cross switched
• Without contact suppression
• Minimum load current 0.5mA rms
• Maximum current 0.5A rms at 20 to 280V

Å

(ac)

• Maximum offstate leakage current 10µA rms
• For resistive loads only, must use RC suppression for

inductive loads

Electromechanical Relay

• Form C contact configuration
• Minimum load current 10mA @ 5V

Î

(dc)

• Rated resistive and inductive loads: 2A @ 250V

Å

(ac) or

30V

Î

(dc) maximum

• Electrical life 100,000 cycles at rated current
• For resistive loads only, must use RC suppression for

inductive loads

Process

• Range selectable: 0-20mA, 4-20mA, 0-5V

Î

(dc),

1-5V

Î

(dc), 0-10V

Î

(dc)

• Reverse or direct acting
• 0 to 10V

Î

(dc) voltage output into 1,000

minimum load

resistance

• 0 to 20mA current output into 800

maximum load

resistance

• Resolution:

dc ranges = 2.5mV nominal
mA ranges = 5µA nominal

• Calibration accuracy:

dc ranges = ±15mV
mA ranges = ±30µA

• Temperature stability 100ppm/°C

Retransmit

• Range selectable: 0-20mA, 4-20mA, 0-5V

Î

(dc),

1-5V

Î

(dc), 0-10V

Î

(dc)

• 0 to 10V

Î

(dc) voltage output into a 1,000

minimum load

resistance

• 0 to 20mA current output into an 800

maximum load

resistance

• Resolution:

dc ranges = 2.5mV nominal
mA ranges = 5µA nominal

• Calibration accuracy:

dc ranges = ±15mV
mA ranges = ±30mA

• Temperature stability 100ppm/°C

Specifications

(2200)

Controller

• Microprocessor-based, user-selectable control modes
• Heat and cool auto-tune for control outputs
• Universal input 1, auxiliary input 2, 4 outputs
• Control outputs user-selectable as on/off, P, PI, PID
• Input sample period; Single input 10Hz (100 msec), dual input

5Hz (200 msec) adjustable digital filter

• Display update; 2Hz (500 msec), adjustable digital filter
• Retransmit output update; 1 Hz (1 second)
• Output update; burst, 0.1 to 999.9 seconds
• Input/Output/Communication isolation
• Displayed in °C, °F, or process units

Operator Interface

• Dual 4-digit LED displays: upper 0.4 in (10.2mm), lower 0.244

in (6.2mm)

• Advance, Up Arrow, Down Arrow, Infinity tactile keys

Standard Conditions For Specifications

• Ambient temperature 77°F/25°C ±3°C, rated line voltage, 50 to

60Hz, 0 to 90% RH non-condensing,
15-minute warm-up

Universal Input 1
Thermocouple

• Type J, K, T, N, C (W5), E, PTII, D (W3), B, R, S thermocouple

types

• >20M

input impedance

• Maximum 20

source resistance

• 30µA open detection bias

RTD

• 2- or 3-wire platinum, 100

• JIS and DIN curves
• Whole or tenth degree indication
• 150µA nominal RTD excitation current

Process

• Range selectable: 0-10V

Î

(dc), 0-5V

Î

(dc),

1-5V

Î

(dc), 0-20mA, 4-20mA,

• Voltage input impedance 20k

• Current input impedance 100

• Minimum current source resistance 1M

• Input resolution 50,000 bits (approx.) at full scale
• mV input impedance 20M

Input 2
Event Input

• Contact or voltage
• 20K

input impedance

• Voltage input: event high state 3 to 36V

Î

(dc),

event low state 0 to 2V

Î

(dc)

• Resistance/contact input: event high state > 23k

, event low

state 0 to 2k

Remote Set Point Input: mA or DC Range

Selectable

• Voltage input impedance 20k

• Current input impedance 100

Advertising