Wa t l o w S e r i e s 9 6

P a r a m e t e r s

6 . 1

Chapter Six
Parameters

6

Home Page

The resting-state display shows one of the following sets of data, depending on controller
setup. The first prompt appears in the top display, the second in the bottom.

The parameters selected in the Custom Menu (Factory Page) will appear here.

Active: Always
Active if Auto-Manual Operation

Mode (User Menu) is set to
[man] (manual), or if there is
an error.

100 r
310 r/w

Range Low 1 to Range

High 1

heat modes: 0.0 to 100.0
cool modes: -100.0 to 0.0
heat/cool modes:

-100.0 to 100.0

[``96]

Process 1

[`5)0] Manual Set Point**

Monitor the Process
1 value and change
manual set point
value.

Active: Always
Active if Event Function

[E`Fn]

(Input 2 Menu) is set to

[``SP]

(event set point), an event con-
dition exists and Auto-Manual
Operation Mode (User Menu) is
set to

[auto] (automatic).

100 r
202 r

Range Low 1 to Range

High 1

[``96]

Process 1

[`5)0] Event Set Point**

Monitor the Process
1 value and Event
Set Point values.

Active: Always
Active if the remote set point is

active and Local or Remote
Mode

[`L-R] (User Menu) is

set to

[```R] (remote) and

Auto-Manual Operation Mode
(User Menu) is set to

[auto]

(automatic).

100 r
202 r

Range Low 1 to Range

High 1

[``96]

Process 1

[`200] Remote Set

Point**

Monitor the Process
1 value and Remote
Set Point values.

Active: Always
Active if the event set point is not

active and Local or Remote
Mode (User Menu) is set to
[```l] (local) or Auto-Manual
Operation Mode (User Menu) is
set to

[auto] (automatic).

[`OFF] will appear when slewing

below the

[rl`1]] value.

100 r
300 r/w

Range Low 1 to Range

High 1

[`OFF] Off

[``96]

Process 1

[`100] Set Point 1

Monitor the Process
1 value and change
the Set Point values.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

*These parameters are added if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
**These parameters are removed if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
NOTE: Refer to Chapter 7 of this manual for information on parameters for creating ramp and soak profiles in Ramping
versions of the Series 96.
NOTE: To see how all the pages, menus and parameters are grouped, refer to the inside back cover of this manual.
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.