Modbus register numbers, Modbus™ register numbers . . . . . a.3, Series 96 modbus register numbers – Watlow Series 96 User Manual

Page 62: Special modbus functions

Advertising
background image

0

Model Number

1

Serial Number 1

2

Serial Number 2

3

Software ID Number

4

Software Revision

5

Date of Manufacture

9

Input 2 Hardware Enabled

16

Output 1 Hardware

17

Output 2 Hardware

18

Output 3 Hardware

19

Output 4 Hardware

24

Disable Nonvolatile Memory

100

Process 1

101

Error 1

103

Percent Output

104

Actual 2

105

Process 2

106

Alarm 2 Status

110

Alarm 3 Status

200

Operation Mode

201

Event Input Status

202

Remote Set Point

203

Ramping Set Point

204

PID Power

205

Prop Term

206

Integral Term

207

Derivative Term

209

System Error

210

Open Loop Error

300

Set Point 1

301

Auto-Manual Operation Mode

304

Auto-tune Set Point 1

305

Auto-tune Start 1

306

Event Set Point 1

310

Manual Set Point

311

Clear Input Errors

316

Local-Remote (L-r)

319

Set Point 2

321

Alarm 2 Low

322

Alarm 2 High

331

Clear Alarms

332

Silence Alarms

340

Alarm 3 Low

341

Alarm 3 High

500

Propband 1

501

Integral 1

502

Reset 1

503

Derivative 1

504

Rate 1

505

Dead Band 1

506

Cycle Time 1

507

Hysteresis 1

509

Burst 1

510

Propband 2

511

Integral 2

512

Reset 2

513

Derivative 2

514

Rate 2

515

Dead Band 2

517

Hysteresis 2

519

Burst 2

600

Sensor Type 1

601

Input 1

602

Range Low 1

603

Range High 1

604

Input Software Filter 1

605

Calibration Offset 1

606

Decimal 1

607

Input Error Latching

611

Input 2

612

Range Low 2

613

Range High 2

615

Calibration Offset 2

700

Output 1

701

Process 1 Type

713

Power Limit Set Point

714

High Power Limit Above

715

High Power Limit Below

717

Output 2

718

Process 2 Type

719

Alarm 2 Type

720

Alarm Hysteresis 2

721

Latching 2

722

Silencing 2

723

Alarm Active Sides 2

724

Alarm Logic 2

725

Alarm Annunciation 2

734

Output 3

736

Alarm 3 Type

737

Alarm Hysteresis 3

738

Latching 3

739

Silencing 3

740

Alarm Active Sides 3

741

Alarm Logic 3

742

Alarm Annunciation 3

900

Units Type

901

°C or °F

902

Failure Mode

903

Manual Default Power

904

Open Loop Detect

1060

Event Function

1061

Event Condition

1100

Ramping Mode

1101

Ramp Rate

1102

Ramp Scale

1208

Program Type

1211

Abort Set Point

1300

Set Point Menu Lock

1301

Operations Page Mode Lock

1302

Setup Page Lock

1304

Custom Menu Lock

1305

Calibration Menu Lock

1314

Program Menu Lock

1400-1415

Custom Prompt Number (1-16)

1500

Ambient Temperature

1501

Ambient A-D Counts

1504

Channel 1 A-D Counts

1505

Channel 2 A-D Counts

1513

Test Display

1514

Test Output

1515

Line Frequency

1601

Restore Factory Calibration

1602

Default Settings

A . 3

A p p e n d i x

Wa t l o w S e r i e s 9 6

Series 96 Modbus Register Numbers

Relative Parameters

Relative Parameters

Relative Parameters

Note: For Absolute Modbus numbers, add 40001 to the Relative number.
Note: Refer to p. 7.7 for Modbus Register Numbers for ramping parameters.

Special Modbus Functions

The following are modbus registers with special functions. Disable Non-volatile Memory (24); Alarm Status
Output 2 (106); Alarm Status Output 3 (110); Auto-Manual Operation Mode (200); Clear Input Errors (311);
Clear Alarms (331); Silence Alarms (332).

A “0” indicates an active state. Send “1” to the register to activate the function. It will automatically reset
to “0” when the function is complete.