Ramping modbus register numbers, Series 96 ramping modbus register numbers – Watlow Series 96 User Manual

Page 59

Advertising
background image

Wa t l o w S e r i e s 9 6

R a m p i n g

7 . 7

Register

Register 106 (Alarm 2 Status)
Register 110 (Alarm 3 Status)

0

No Alarm Exists

1

Alarm High State

2

Alarm Low State

3

Alarm High Latched State

4

Alarm Low Latched State

5

Alarm High Silenced State

6

Alarm Low Silenced State

7

Alarm High Latched & Silenced State

8

Alarm Low Latched & Silenced State

9

Alarm Waiting for In Range State

10

Alarm Disabled State

11

Alarm Error State

*

Register is disabled or unavailable.

1

Register is only available if program type is set to Time.

2

Register is only available if program type is set to Rate.

3

Register is only available if step type is set to Set Point.

4

Register is only available if step type is set to Soak.

5

Register is only available if step type is set to Jump.

6

Register is only available if step type is set to End.

Note:

Data to be written to registers that are unavailable for a particular step type will be ignored.

File 1
Step 1

5020
5021
5022
5023
5024
5025
5026
5027

5028

5029
5030
5031
5032

File 1
Step 2

5033
5034
5035
5036
5037
5038
5039
5040

5041

5042
5043
5044
5045

File 1
Step 3

5046
5047
5048
5049
5050
5051
5052
5053

5054

5055
5056
5057
5058

File 1
Step 4

5059
5060
5061
5062
5063
5064
5065
5066

5067

5068
5069
5070
5071

File 1
Step 5

5072
5073
5074
5075
5076
5077
5078
5079

5080

5081
5082
5083
5084

File 1
Step 6

5085
5086
5087
5088
5089
5090
5091
5092

5093

5094
5095
5096
5097

File 1
Step 7

5098
5099
5100
5101
5102
5103
5104
5105

5106

5107
5108
5109
5110

File 1
Step 8

5111
5112
5113
5114
5115
5116
5117
5118

5119

5120
5121
5122
5123

File 2
Step 1

5124
5125
5126
5127
5128
5129
5130
5131

5132

5133
5134
5135
5136

File 2
Step 2

5137
5138
5139
5140
5141
5142
5143
5144

5145

5146
5147
5148
5149

File 2
Step 3

5050
5151
5152
5153
5154
5155
5156
5157

5158

5159
5160
5161
5162

File 2
Step 4

5163
5164
5165
5166
5167
5168
5169
5170

5171

5172
5173
5174
5175

File 2
Step 5

5176
5177
5178
5179
5180
5181
5182
5183

5184

5185
5186
5187
5188

File 2
Step 6

5189
5190
5191
5192
5193
5194
5195
5196

5197

5198
5199
5200
5201

File 2
Step 7

5202
5203
5204
5205
5206
5207
5208
5209

5210

5211
5212
5213
5214

File 2
Step 8

5215
5216
5217
5218
5219
5220
5221
5222

5223

5224
5225
5226
5227

Parameter

Step Type
End Set Point
Hours

1 or 4

Minutes

1 or 4

Seconds

1 or 4

Rate

2 and 3

EventOutput

2, 3 or 4

Waitfor Event

Input

4

Waitfor Deviation

(Process Input)

4

Jump File

5

Jump Step

5

Jump Count

5

End Type

6

Profile Definition Registers
(Read and Write)

Note:

For absolute numbers, add 40001 to each relative
number.

41210

1209

Resume Profile

1

41211

1210

Hold Profile

1

40001

4000

Start File

1 or 2

40002

4001

Start Step

1 - 8

40003

4002

Start Profile

5

45001

5000

File

45002

5001

Step

45003

5002

Step Type

45004

5003

Wait for Event Input

4

45005

5004

Wait for Deviation (process input)

4

45006

5005

Event Output

45007

5006

Hours

45008

5007

Minutes

45009

5008

Seconds

45010

5009

Current Set Point

45011

5010

Jump Count

45012

5011

End Set Point

45013

5012

Rate

45014

5013

Profile State

Command Registers (Write Only) Send to
activate

Absolute

Relative

Parameter

Monitor Current Profile Registers (Read Only)

Series 96 Ramping Modbus Register Numbers

NOTE: For more information about communicating with Watlow controllers, go to www.watlow.com and download the Data
Communications Reference: Electronic User’s Manual. It is located under Literature, User’s Manuals, English and search
on data communications reference
.

Advertising