8. BRAIN TERMINAL BT200 OPERATION

(4) Output Signal Low Cut Mode Setup

(D10: LOW CUT, D11: LOW CUT MODE)

Low cut mode can be used to stabilize the output
signal near the zero point. The low cut point can be set
in a range from 0 to 20% of output. (Hysteresis:

±1%)

Select “ZERO” as the low cut mode.

(%)

50

20

0

50 (%)

Output

Input

᭹ Low cut mode “ZERO”

F0816.EPS

• Example: Change the low cut setting range

from 10% to 20%, and the low
cut mode from LINEAR to ZERO.

FEED

NO

OK

SET
D11:LOW CUT MODE
ZERO

Use the or key

to select “ZERO.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0817.EPS

FEED

NO

OK

SET
D10:LOW CUT
20.0 %

ESC

SET
D11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >

DATA

DIAG

PRNT

ESC

PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D20:DISP SELECT
NORMAL %

CLR

ESC

SET
D10:LOW CUT
10.0 %
+ 20.0

Set 20.

Press the key twice to

enter the setting.

Press the (OK) key.

Next, the [D11: LOW CUT MODE]

setting panel is displayed.

(5) Change Output Limits

(D15:OUT LIMIT(L), D16:OUT LIMIT(H))

The range of normal output is preset at factory from
-5.0 to 110.0% unless otherwise specified, and the
output is limited with these upper and lower values.
This output range can be changed, for example, to
meet the requirements of NAMUR, etc. within the
settable range. Set the lower limit with D15:OUT
LIMIT(L)
and upper limit with D16:OUT LIMIT(H).

Settable range : -5.0 to 110.0 (%)

Lower limit < Upper limit

(6) Integral Indicator Scale Setup

The following 5 displays are available for integral
indicators.

T0808.EPS

D20: DISP SELECT

and Display

NORMAL %

USER SET

USER & %

INP PRES

PRES & %

Indicates –5 to 110% range
depending on the Measurement
range (C21, C22).

Indicates values depending on the
Engineering range (D22, D23).

(

Note 1

)

Units set using Engineering unit
(D21) are not indicated.

Indicates user set and % alternately
in 3 second intervals.

Indicates input pressure.

(

Note 2

)

Indication limits –19999 to 19999.

Indicates input pressure and %
alternately in 3 second intervals.

A10:OUTPUT (%)

45.6 %

Description

and Related parameters

A11:ENGR.OUTPUT

20.0 M

A10:OUTPUT (%)

45.6 %

A11:ENGR. OUTPUT

20.0 M

A40:INPUT

456 kPa

A10:OUTPUT (%)

45.6 %

A40:INPUT

456 kPa

(Note 1) Scale range can be specified with range limit specifications up

to 5 digits (excluding any decimal point) for low or high range

limits within the range of –19999 to 19999.

The range with decimals is available to the third decimal place.

(Note 2) It indicates the value after zeroing.

See (a.) through (c.) for each setting procedure.

Advertising
This manual is related to the following products: