10-5

10. GENERAL SPECIFICATIONS

10.3

Optional Specifications

For F

OUNDATION

Fieldbus explosion protected type, see IM 01C22T02-01E.

For PROFIBUS PA explosion protected type, see IM 01C22T03-00E.

Item

Description

Code

Factory Mutual (FM)

CENELEC ATEX (KEMA) Intrinsically safe Approval

*2

Certificate: KEMA 02ATEX1030X

II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60

ЊC (–40 to 140ЊF)

Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730

␮H

KS2

FM Intrinsically safe Approval

*1

Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,

Groups E, F & G and Class III, Division 1 Hazardous Locations.

Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,

Groups E, F & G, and Class III, Division 1 Hazardous Locations.

Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60

ЊC (–40 to 140ЊF)

Intrinsically Safe Apparatus Parameters

[Groups A, B, C, D, E, F and G]

Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730

␮H

[Groups C, D, E, F and G]

Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730

␮H

FS1

CENELEC ATEX (KEMA) Flameproof Approval

*2

Certificate: KEMA 02ATEX2148

II 2G EExd IIC T4, T5, T6

Amb. Temp.: T5; –40 to 80

ЊC ( –40 to 176ЊF), T4 and T6; –40 to 75ЊC ( –40 to 167ЊF)

Max. process Temp.: T4; 120

ЊC (248ЊF), T5; 100ЊC (212ЊF), T6; 85ЊC (185ЊF)

KF2

FM Explosionproof Approval

*1

Explosionproof for Class I, Division 1, Groups B, C and D

Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G

Hazardous (classified) locations, indoors and outdoors (NEMA 4X)

Temperature class: T6

Amb. Temp.: –40 to 60

ЊC (–40 to 140ЊF)

FF1

FU1

Combined FF1 and FS1

*1

Combined KF2, KS2 and Type n

*2

Type n

II 3G Ex nL IIC T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)

Ui=30 V DC, Ci=22.5 nF, Li=730 µH

Dust

II 1D maximum surface temperature T65°C (149

ЊF) {Tamb.: 40°C (104ЊF)},

T85°C (185

ЊF) {Tamb.: 60°C (140ЊF)}, T105°C (221ЊF) {Tamb.: 80°C (176ЊF)}

KU2

CENELEC ATEX

T1004-1.EPS

*1:

Applicable for Electrical connection code 2 and 7 (1/2 NPT female).

*2:

Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).