IM 01C21C01-01E

9-5

9. MAINTENANCE

NOTE

Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket
prior to tightening the two bosses. If it is not, the
zero-adjustment mechanism will be damaged.

5) Replace the cover.

9.4.3 Replacing the Process Connector

Gasket

This subsection describes the procedure for replacing
the process connector gasket. (See Figure 9.4.3.)

1) Loosen the two bolts and remove the process

connector.

2) Replace the process connector gasket.
3) Mount the process connector. Tighten the bolts

securely and uniformly to a torque of 39 to 49 N·m
{4 to 5 kgf·m}, and verify that there are no pressure
leaks.

Process connector

gasket

Process connector

Bolt

F0904.EPS

Figure 9.4.3 Replacing the Process Connector Gasket

9.5 Troubleshooting

If any abnormality appears in the measured values, use
the troubleshooting flow chart below to isolate and
remedy the problem. Since some problems have
complex causes, these flow charts may not identify all.
If you have difficulty isolating or correcting a problem,
contact Yokogawa service personnel.

9.5.1 Basic Troubleshooting

First determine whether the process variable is actually
abnormal or a problem exists in the measurement
system.

If the problem is in the measurement system, isolate
the problem and decide what corrective action to take.

This transmitter is equipped with a self-diagnostic
function which will be useful in troubleshooting; see
Section 8.5 for information on using this function.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variable

itself abnormal?

Inspect the

process system.

Isolate problem in

measurement system.

Does problem exist in
receiving instrument?

Check/correct

environmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operating

conditions.

Measurement system problem

F0905.EPS

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 9.5.1 Basic Flow and Self-Diagnostics