Indication and input pressure indication, User-set engineering unit display – Yokogawa EJA220A User Manual

Page 42

Advertising
background image

IM 01C21C01-01E

8-10

8. BRAIN TERMINAL BT200 OPERATION

% indication and
input pressure
indication

Transmitter is set

for “% display” when

shipped.

D20: DISP SELECT
NORMAL %
INP PRES
PRES & %

User-set engineering
unit display

D20: DISP SELECT
USER SET
USER & %

D21: DISP UNIT

D22: DISP LRV

D23: DISP HRV

Set for user-set
engineering unit display.

Set a unit to be
displayed on the BT200.

Set a numeric value for
engineering unit for 4 mA
output (LRV).

Set a numeric value for
engineering unit for 20 mA
output (HRV).

F0818.EPS

a. Display Selection (D20: DISP SELECT)

Follow the instructions given to the below to change
the range of integral indication scales.

When USER SET is selected, the user set values of
integral indication and A11: ENGR. OUTPUT
parameter are indicated.

• Example: Set the integral indicator scale to

engineering units display.

The “%” disappears from the

integral indicator display.

ESC

SET
D20:DISP SELECT
USER SET

FEED

NO

OK

SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>

Use the or key

to select “USER SET.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0819.EPS

b. Setting User-set Engineering Unit

(D21: DISP UNIT)

This parameter allows entry of the engineering units to
be displayed on the BT200. When the instrument is
shipped, this is set as specified in the order.

Follow the procedure below to change this setting.

This parameter need not be set for % display.

• Example: Set an engineering unit M.

CODE

CAPS

CLR

ESC

SET
D21:DISP UNIT
M

FEED

NO

OK

SET
D21:DISP UNIT

M_

Set “M.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0820.EPS