IM 01C21C01-01E

8-16

8. BRAIN TERMINAL BT200 OPERATION

8.4 Displaying Data Using the

BT200

8.4.1

Displaying Measured Data

The BT200 can be used to display measured data.

The measured data is updated automatically every 7
seconds. In addition, the display can be updated to the
present data value at any time by pressing the
(DATA) key. For parameters associated with the
display of measured data, see Subsection 8.3.1,
“Parameter Summary.”

• Example: Display output.

DATA

DIAG

PRNT

ESC

PARAM
A10:OUTPUT (%)

A11:ENGR.OUTPUT

A20:AMP TEMP

HOME

SET

ADJ

ESC

MENU
A:DISPLAY
B:SENSOR TYPE

F0836.EPS

Data is updated automatically
at 7-second intervals.

Display “A10: OUTPUT (%).”

PARAM
A10:OUTPUT (%)
XX.X %
A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C

communi

8.4.2 Display Transmitter Model and

Specifications

The BT200 can be used to display the model and
specifications of the transmitter.

• Example: View transmitter model name.

HOME

SET

ADJ

ESC

MENU
A:DISPLAY
B:SENSOR TYPE

DATA

DIAG

PRNT

ESC

PARAM
B10:MODEL
EJA210A-DM
B11:STYLE NO.
S1.01
B20:LRL
– 98.07 kPa

Press .

F0837.EPS

For the associated
parameters, see Subsection
8.3.1, Parameter Summary.

8.5 Self-Diagnostics

8.5.1

Checking for Problems

(1) Identifying Problems with BT200

The following four areas can be checked.
(a) Whether connections are good.
(b) Whether BT200 was properly operated.
(c) Whether settings were properly entered.
(d) History of the errors.
See examples below.

• Example 1: Connection errors

ESC

communication error

Press the key.

When the panel shown on the left

appears, press the key.

Since communications will be

unsuccessful if there is a problem

in the connection to the BT200, the

display at the left will appear.

Recheck the connection.

Press the (OK) key.

––WELCOME––

BRAIN TERMINAL
ID: BT200

check connection
push ENTER key

UTIL

FEED

• Example 2: Setting entry errors

F0838.EPS

The initial data panel shows the

result of current transmitter

diagnostics.

DATA

DIAG

PRNT

ESC

PARAM
C20:PRESS UNIT
kPa
C21:LOW RANGE
600 kPa
C22:HIGH RANGE
600 kPa

FEED

PRNT

ESC

DIAG
C60:SELF CHECK
ERROR
< ERROR >
< ILLEGAL LRV >

Press the (DIAG) key in the

parameter panel to go to the

diagnostics panel

(C60: SELF CHECK).

An error message is displayed

when an error occurs in the

diagnostics panel.

OK

PARAM
01:MODEL
EJA210A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
ERROR