IM 01C21C01-01E

8-15

8. BRAIN TERMINAL BT200 OPERATION

Span adjustment value (%) =

P

1

: Actual differential pressure/pressure value

A40: Input (indicated as the value after zeroing)

Measurement pressure

Applied pressure

P

1

Ϫ A40

P

1

ϫ

100

A40

P

1

0

F0846.EPS

• Example: For the range of 0 to 30 kPa.

A40: INPUT = 30.15 kPa

J15: SPAN ADJ = 0.15 %

Suppose that a standard pressure of 30 kPa is applied and
the value of the parameter of A40: INPUT is 30.15 kPa.
Firstly, obtain the slope error for the span as follows;

Add

Ϫ0.5% to 0.15% of the current value to calculate the

accumulated span adjustment value.

0.15

ϩ (Ϫ0.50) = Ϫ0.35

F0847.EPS

FEED

NO

OK

SET
J15:SPAN ADJ
-0.35 %

ESC

CLR

DEL

SET
J15:SPAN ADJ
0.15 %
- 0.35

Set

Ϫ0.35.

Press key twice.

Press the (OK) key.

30.00

Ϫ30.15

30.00

ϫ 100 = Ϫ0.5 (%)

ϭ

Span adjustment value (%) =

Note: Enter 0.00 to J15: SPAN ADJ to reset the

span adjustment to the initial value at the
shipment.

P

1

Ϫ

A40

P

1

ϫ100

(15)

Test Output Setup (K10: OUTPUT X%)

This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.

• Example: Output 12 mA (50%) fixed current.

ESC

SET
K10:OUTPUT X %
50.0 % ACTIVE

FEED

NO

OK

SET
K10:OUTPUT X %
0.0 %
+ 050.0

Set 50.0%.

Press the key twice to

output a fixed current at 50%.

“Active” is displayed while this is

being executed.

Press the (OK) key to cancel

the fixed current output.

F0834.EPS

IMPORTANT

1. Test output is held for approximately 10

minutes, and then released automatically after
the time has elapsed. Even if the BT200 power
supply is turned off or the communication cable
is disconnected during test output, it is held for
approximately 10 minutes.

2. Press the

(OK) key to release test output

immediately.

(16)

User Memo Fields (M: MEMO)

This feature provides 5 user memo fields, each holding
up to 8 alphanumeric characters. Up to 5 items such as
inspection date, inspector, and other information can be
saved in these fields.

• Example: Save an inspection date of January

30, 1995.

DATA

DIAG

PRNT

ESC

SET
M10:MEMO 1

95.1.30_

ESC

PARAM
M10:MEMO 1

M20:MEMO 2

M30:MEMO 3

Set 95.1.30 in the order of year,

month, and day.

Press the key twice to

enter the setting.

F0835.EPS