3. OPERATION

3.2.3

Setting Parameters

Set or change the parameters as necessary. After
completing these, do not fail to use the “DIAG” key to
confirm that “GOOD” is displayed for the self-
diagnostic result at _

60: SELF CHECK

.

(1) Tag No. Setup (C10: TAG NO)

Use the procedure below to change the Tag No. Up to
16 alphanumeric characters can be entered.

Press the key to turn on
the BT200.

Connect DPharp and BT200 using
a communication cable and press
the key.

PARAM
01:MODEL
EJX110 M
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD

OK

MENU
A:DISPLAY
B:SENSOR TYPE
C:BASIC SETUP
D:AUX SET1
E:AUX SET2
G:ALARM SET

HOME

SET

ADJ

ESC

MENU
C:BASIC SETUP
D:AUX SET 1
E:AUX SET 2
G:ALARM SET
H:AUTO SET
I:DISP SET

HOME

SET

ADJ

ESC

MENU
C10:TAG NO.
YOKOGAWA
C20:PRES UNIT
kPa
C21:PRES LRV
0.00000 kPa

DATA

DIAG

PRNT

ESC

<When power is off>

Select C: BASIC SETUP and press
the key.

Select C10: TAG NO. and press
the key.

Displays the name of connected
DPharp model, TAG NO. and
diagnostics information. Press the
(OK) key after confirmation.

Press the (SET) key to
display the SET menu panel.

––WELCOME––

BRAIN TERMINAL
ID: BT200

check connection
push ENTER key

UTIL

FEED

F0308.EPS

SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA

CODE

CAPS

CLR

ESC

When you have made an entry mistake, return
the cursor using the key, then reenter.

Set the new TAG NO. (FI1-1a).

F

OKOGAWA

FIKOGAWA

FI1OGAWA

FI1-GAWA

FI1-1AWA

FI1-1aWA

FI1-1a

Set TAG NO. and press the
key.

SET
C10:TAG NO.
YOKOGAWA
FI1-1a _

CODE

caps

CLR

ESC

• Example: Set a Tag No. to FI1-1a

SET
C10:TAG NO.
FIC-1a

FEED

NO

OK

DATA

DIAG

PRNT

ESC

This is the panel for confirming

set data. The set data items flash.

When all items have been confir-

med, press the

again. (To go back to the setting

panel, press the (NO) key.

SET
C10:TAG NO.
YOKOGAWA
FIC-1a

print off
F2:printer on

PARAM
C10:TAG NO.
FIC-1a
C20:PRES UNIT
kPa
C21:PRES LRV
0.00000 kPa

FEED

POFF

NO

The DPharp TAG NO. was

overwritten.

Press the (OK) key to

return to the parameter panel.

Press the (NO) key to

return to the setting panel.

F0309.EPS

(2) Calibration Range Setup

a. Setting Calibration Range Unit

(C20: PRES UNIT)

The unit parameter is set at the factory before shipment
if specified at the time of order. Follow the procedure
below to change the unit parameter.

• Example: Change the unit from mmH2O to kPa.

ESC

SET
C20:PRES UNIT
kPa

FEED

NO

OK

SET
C20:PRES UNIT
mmH2O
< mmWG >
< mmHg >
< Torr >
< kPa >

Use the or

key to select kPa.

Press the key twice

to enter the setting.

Press the (OK) key.

F0310.EPS

Note that the Yokogawa default setting for the standard
temperature is 4

ЊC (39.2ЊF). For the units of mmH

2

O,

mmAq, mmWG, inH

2

O, and ftH

2

O, the pressure varies

according to the standard temperature definition. When
a standard temperature of 20

ЊC (68ЊF) is required,

select @20degC (68.0F) at the parameter of D16:H2O
UNIT SEL.

Available pressure units are shown below.

FX0301.EPS

mmH2O
mmAq
mmWG
mmHg
Torr
kPa

MPa
mbar
bar
gf/cm2
kgf/cm2
inH2O

inHg
ftH2O
psi
atm
Pa
hPa