3. OPERATION

(20)

Capillary Fill Fluid Density Compensa-
tion (E10: T.ZERO CMP, E11: TEMP
ZERO)

For transmitters with diaphragm seals, this function is
used to compensate the zero shift caused by the
ambient temperature effect on the capillary tubes.

The following equation indicates the relationship
between the calculated output value and the compen-
sating constant K (%/

ЊC) with the measured ambient

temperature at the capsule module.

Compensated output

ϭ

output

ϩ

K

ϫ

Tamb

(1) Temperature Compensation Mode Setup

(E10: T. ZERO CMP)
When using this function, set T. ZERO CMP to ON
to enable or OFF to disable. To set to ON, follow
the procedure below.

ESC

SET
E10:T.ZERO CMP
OFF
< OFF >
< ON >

OK

FEED

NO

SET
E10:T.ZERO CMP
ON

• Example: Set the temperature compensation

mode to ON.

Use the or key

to select ON.

Press the key twice to

enter the setting.

Press the (OK) key.

F0355.EPS

(2) Zero Shift Compensation Setup

(E11: TEMP ZERO)
Obtain the K compensating value from the equa-
tion(1) below.

K= – h

×

B

×

100 ................ (a)

Span

where,

B: Constant value of fill fluid (See Table A.)

span: |URV–LRV|

h: Distance from high pressure side to low

pressure side (m)

EJX118A: Distance from high side of
diaphragm seal to low side of diaphragm seal.

EJX438A: Distance from diaphragm seal (high
side) to position of transmitter (low side).

Transmitter

L

h

0

H

(

ϩ

)

EJX118A

F0357.EPS

h

h

L

L

H

Transmitter

Transmitter

0

(

ϩ

)

(

Ϫ

)

EJX438A

Note: When the transmitter is positioned lower than the

diaphragm seal part, the value of “h” must have a

negative sign (

Ϫ

).

Enter “–0.149.”

Press the key twice to

enter the setting.

F0358.EPS

ESC

SET
E11:TEMP ZERO
0.000 %/degC
- 00.149

CLR

OK

SET
E11:TEMP ZERO
-0.149 %/degC

NO

FEED

K

ϭϪ

(

ϩ

3)

ϫ

0.00745

Ϭ

15

ϫ

100

ϭϪ

0.149

Press the (OK) key.

• Example: Enter K value obtained from the

equation (a). A value having up to 3

decimal places may be specified.

When h

ϭϩ

3 m, Fill fluid code A, span

ϭ

15 kPa,

Note 1: The function is performed using in a built-in temperature

sensor in the transmitter body. The temperature deviation
between the transmitter body and capillaries should be
minimized to achieve optimal performance of the function.

Note 2: When the span changes, reenter the newly obtained value of

K to E11: TEMP ZERO.

Table A. Constant value [B] of fill fluid

T0308.EPS

Fill fluid

A, C

B

D

E

code
mmH

2

O 0.76

0.87

1.45

0.75

kgf/cm

2

0.000076 0.000087 0.000145 0.000075

kPa 0.00745

0.00853

0.01422

0.00736

mBar 0.07453

0.08532

0.14220

0.07355

atm 0.000074

0.000084

0.000140

0.000073

inH

2

O 0.02992 0.03425

0.05709

0.02953

psi 0.00108

0.00124

0.00206

0.00167

mmHg 0.05592 0.06401 0.10669 0.05518

Constant v

alue [B]

Note 3: Select the unit of constant value of [B] from the actual unit

used for the transmitter in operation.

Advertising
This manual is related to the following products: