(12) Output Status Setup when a Hardware

Error Occurs (D26: ERROR OUT)

This parameter allows the setting of the output status
when a hardware error occurs. The following selections
are available.

(a) BURNOUT DIR; Outputs the corresponding values

of 110% or –5% of output signals according to the
setting by burnout direction switch (BO) on the
CPU board.

(b) HOLD; Outputs the last value held before the error

occurred.

Note: A hardware error means CAP.ERR of AL.01 or AMP.ERR of

AL.02 which are shown in table 4.2 Alarm Message
Summary.

• Example: Set the output status to HOLD when

a hardware error occurs.

ESC

SET
D26:ERROR OUT
BURNOUT DIR
< BURNOUT DIR >
< HOLD >

Use the or key

to select HOLD.

Press the key twice to

enter the setting.

F0326.EPS

Then press the (OK) key.

(13) Bi-directional Flow Measurement Setup

(E30: BI DIRE MODE)

(a) This parameter enables selection of 50% output at

an input of 0 kPa.
Procedure is shown in the figure below.

(b) Combining this with

C40: OUTPUT MODE

provides a square root output computed indepen-
dently for 0% to 50% output and for 50% to 100%
output.

• Example: If measurement range is 0 to 10 kPa

(LRV=0 kPa, URV=10 kPa)

The measurement range changes to –10 to 0 to 10 kPa

(output 0% to 50% to 100).

Note that C21: PRES LRV and C22: PRES URV

are not changed.

ESC

SET
E30:BI DIRE MODE
OFF
< OFF >
< ON >

Use the or key

to select ON.

Press the key twice to

enter the setting.

F0327.EPS

Then press the (OK) key.

20 mA (100% display)

4 mA (–100% display)

Output mode “LINEAR”

LRV

HRV

F0328.EPS

20 mA (100% display)

Low Cut

4 mA (–100% display)

Output mode “SQUARE ROOT”

LRV

HRV

(14) Range Change while Applying Actual

Inputs (H10: AUTO P LRV, H11: AUTO P
URV)

This feature allows the lower and upper range values to
be set up automatically with the actual input applied. If
the lower and upper range values are set, C21: PRES
LRV and C22: PRES URV are changed at this same
time.

Follow the procedure in the figure below.
The measurement span is determined by the upper and
lower range values. Changing the lower range value
results in the upper range value changing auto-
matically, keeping the span constant.

• Example 1: When changing the lower range

value to 0.5 kPa for the present

setting of 0 to 30 kPa, take the
following action with input pressure
of 0.5 kPa applied.

FEED

NO

OK

SET
H10:AUTO P LRV
0.5000 kPa

DATA

DIAG

PRNT

ESC

PARAM
H10:AUTO P LRV
0.5000 kPa
H11:AUTO P URV
30.500 kPa
H20:AUTO SP LRV
0.0 MPa

ESC

SET
H10:AUTO P LRV
0 kPa
+ 0

F0329.EPS

The upper range value is changed

keeping the span constant.

Parameters C21 and C22 are

changed at the same time.

Press the key twice.

The lower range value is changed

to 0.5 kPa.

Press the (OK) key.

Note that changing the upper range value does not
cause the lower range value to change but does change
the span.