16) test output setup (k10: output x %), 17) signal characterizer – Yokogawa EJX440A User Manual

Page 25

Advertising
background image

IM 01C25T03-01E

3-17

3. OPERATION

c. Sensor Trim for Static Pressure

(J21: SP ZERO ADJ, J22: SP SPAN ADJ,
J25: SP ZERO DEV, J26: SP SPAN DEV)

For the EJX differential transmitters (Except for
EJX120A), zeroing and full sensor trim of the static
pressure is performed in the same way as with the
primary process variable (PV). Note that the static
pressure sensor trim should be done only after trim-
ming the PV.

d. Reset Trim Adjustment to Factory Setting

(J56: CLEAR ADJ)

Use

PRES

or

SP

of J56: CLEAR ADJ parameter to

reset the trim adjustment to the initial calibrated values
that were set. When

PRES

is selected to clear the

adjustment, the amount of the adjustment by the
external zero-adjustment screw is returned to the initial
setting as well.

• Example: Reset the trim adjustment of pressure

to factory set characterization curve.

ESC

SET
J56:CLEAR ADJ
---

FEED

NO

OK

Use the or key

to select PRES.

Press the key twice to

enter the setting.

Press the (OK) key.

F0353.EPS

SET
J56:CLEAR ADJ
---
< --- >
< PRES >
< SP >
< 4-20mA >

(16)

Test Output Setup (K10: OUTPUT X %)

This feature can be used to output a fixed current for
loop checks. The available range for test output
depends on the setting at parameters of D20 OUT
LIMIT (L) and D21 OUT LIMIT (H), whose limit is
from 3.6 mA (–2.5%) to 21.6 mA (110%).

• Example: Output 12 mA (50%) fixed current.

CLR

ESC

SET
K10:OUTPUT X %
50.00% ACTIVE

FEED

NO

OK

SET
K10:OUTPUT X %
0.00 %
+ 050.00

Set 50.00%.

Press the key twice to

output a fixed current at 50%.

Active is displayed while this is

being executed.

Press the (OK) key to cancel

the fixed current output.

F0336.EPS

IMPORTANT

1. Test output continues for approximately 10

minutes, then is released automatically. Even if
the BT200 power supply is turned off or the
communication cable is disconnected, test
output will continue for approximately 10
minutes.

2. Press the

(OK) key to release test output

immediately.

(17)

Signal Characterizer

This function is used to compensate the output for non-
linear applications. The characterized values are
applied to the 4-20 mA output. For the measured
pressure, a maximum of nine coordinates can be
specified between 0-100%. Perform the coordinate
settings while the T10: S. C. ENABLE parameter is

INHIBIT

.

To apply the settings to the output, set the T10: S. C.
ENABLE parameter to

ENABLE

.

Note that the EJX rejects the activation of the function
by AL. 60 with the following transmitter’s status:

• When the specified coordinates of x and y are not

incremental as the input increases.

• When the output mode of the output signal is set as

SQUARE ROOT

; at the same time, the low cut

mode is set to

LINEAR

.

Advertising