IM 01C25T03-01E

3-10

3. OPERATION

a. Display Selection

(I10: DISP OUT1)

Select the variable for the parameter I10: DISP OUT1
to display on the integral indicator.

• Example: Change the integral indicator scale

from % of range to input pressure

display.

ESC

SET
I10:DISP OUT1
PRES

FEED

NO

OK

Use the or key

to select PRES.

Press the key twice to

enter the setting.

Press the (OK) key.

F0318.EPS

SET
I10:DISP OUT1
PRES %
< PRES >
< PRES % >
< ENGR.PRES >
< SP >

b. Cyclic Display

(I11: DISP OUT2, I12: DISP OUT3, and I13:
DISP OUT4)

In addition to the display set at I10: DISP OUT1,
displays can be set at I11: DISP OUT2, I12: DISP
OUT3, and I13: DISP OUT4 for cyclic display in the
order of the parameter number.

c. User Setting of Engineering Unit and Scale

(I30: ENGR.UNIT, I31: EASY EU SET, I33:
ENGR.LRV, and I34: ENGR.URV)

These parameters allow the entry of the engineering
units and scale to be displayed. The engineering unit
can be selected from the parameter of I31: EASY EU
SET as listed below. Alternately, up to eight alphanu-
merics, spaces, and a slash “/” can be input on keypad
at I30: ENGR.UNIT; only first six are displayed on the
integral indicator.

Select the unit from the list of I31: EASY EU SET.

FX0302.EPS

kPa
MPa
mbar
bar
psi
psia
mmH2O
mmHg
mmHgA
mmAq
mmWG
Torr
inH2O
inHg
inHgA

ftH2O
gf/cm2
kgf/cm2
kg/cm2G
kg/cm2A
atm
kg/h
t/h
m3/h
m3/min
l/h
l/min
kl/h
kl/min
Nl/h

Nl/min
Nm3/h
Nm3/min
ACFH
ACFM
SCFH
SCFM
GPH
GPM
m
mm
in
ft
kg/m3
g/cm3

Follow the procedure below to change the settings.

• Example: Set an engineering unit M.

CODE

CAPS

CLR

ESC

SET
I30:ENGR.UNIT
M

FEED

NO

OK

SET
I30:ENGR.UNIT

M_

Set M.

Press the key twice to

enter the setting.

Press the (OK) key.

F0319.EPS

Note that following symbols are not available.

. – , + * ) ( ’ & % $ # ” !

The transmitter integral indicator shows “-- -- -- -- -- --”
when these are entered.

• Example: Set lower range value (LRV) to –50

and upper range value (URV) to 50.

FEED

NO

OK

SET
I34:ENGR.URV
50 M

Press the (OK) key.

F0320.EPS

DEL

CLR

ESC

DATA

DIAG

PRNT

ESC

PARAM
I32:ENGR.EXP
---
I33:ENGR.LRV
– 50 M
I34:ENGR.URV
50 M

DEL

CLR

ESC

SET
I33:ENGR.LRV
0.00 M
- 50

Set –50.

Press the key twice to

enter the setting.

Setting LRV

Setting URV

Set 50.

Press the key twice to

enter the setting.

SET
I34:ENGR.URV
100.00 M
+ 50

FEED

NO

OK

SET
I33:ENGR.LRV
- 50 M

Press the (OK) key.