IM 01C25T03-01E

3-8

3. OPERATION

(4) Output Mode and Integral Indicator Dis-

play Mode Setup (C40: OUTPUT MODE,
I20: P DISP MODE)

The mode setting for the output signal and the integral
indicator can be performed independently.

This mode is set as specified in the order when the
instrument is shipped. Follow the procedure below to
change the mode.

If the instrument is equipped with an integral indicator
and the display mode is

SQUARE ROOT

, “

” is

displayed on the integral indicator.

• Output mode for 4-20 mA output

• Example: Set output mode from Linear to

Square root.

ESC

SET
C40:OUTPUT MODE
SQUARE ROOT

FEED

NO

OK

SET
C40:OUTPUT MODE
LINEAR
< LINEAR >
< SQUARE ROOT >

Use the or key

to select SQUARE ROOT.

Press the key twice to

enter the setting.

Press the (OK) key.

F0314.EPS

• Integral indicator display mode

• Example: Set display mode from Linear to

Square root.

ESC

SET
I20:P DISP MODE
SQUARE ROOT

FEED

NO

OK

SET
I20:P DISP MODE
LINEAR
< LINEAR >
< SQUARE ROOT >

Use the or key

to select SQUARE ROOT.

Press the key twice to

enter the setting.

Press the (OK) key.

F0315.EPS

(5) Output Signal Low Cut Mode Setup

(D10: LOW CUT, D11: LOW CUT MODE)

Low cut mode can be used to stabilize the output
signal near the zero point. The low cut point can be set
in a range from 0 to 20%, the direct ratio correspond-
ing to the output signal of 4 to 20 mA. (Hysteresis:

±

10% of the cut point)

Either

LINEAR

or

ZERO

can be selected as the low

cut mode. Unless otherwise specified, the cut mode is
set to LINEAR at the factory.

Note that when the output modes of the output signal
and the integral indicator are selected as

SQUARE

ROOT

and

LINEAR

accordingly, the low cut function

is not available for the integral indicator display.

• Example: Change the low cut setting range

from 10% to 20%, and the low
cut mode from LINEAR to ZERO in
the SQUARE ROOT output mode.

FEED

NO

OK

SET
D11:LOW CUT MODE
ZERO

Use the or key

to select ZERO.

Press the key twice to

enter the setting.

Press the (OK) key.

F0317.EPS

FEED

NO

OK

SET
D10:LOW CUT
20.00 %

ESC

SET
D11:LOW CUT MODE
LINEAR
< LINEAR >
< ZERO >

DATA

DIAG

PRNT

ESC

PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D15:H/L SWAP
NORMAL

CLR

ESC

SET
D10:LOW CUT
10.00 %
+ 20.00

Set 20.

Press the key twice to

enter the setting.

Press the (OK) key.

Next, the [D11: LOW CUT MODE]

setting panel is displayed.

(%)

50

20

0

50 (%)

Output

Low cut mode “LINEAR”

Input

(%)

50

20

0

50 (%)

Low cut mode “ZERO”

LOW CUT at 20%

Input

Advertising