8) operation mode setup (d22: rev output) – Yokogawa EJX440A User Manual

Page 19

Advertising
background image

IM 01C25T03-01E

3-11

3. OPERATION

d. Setting Static Pressure Unit and Scale

(D30: SP UNIT, D33: SP LRV, and D34: SP
URV)

Static pressure can be displayed in measured input
static pressure or in %, independent from the 4-20 mA
output signal of measured pressure or differential
pressure. These parameters allow the entry of the static
pressure unit and scale to be displayed.

Note that the parameter D37: SP SELECT can be used
to select either the high or low pressure side of the
capsule to monitor the static pressure.

(7) Unit Setup for Displayed Temperature

(D40: TEMP UNIT)

When the instrument is shipped, the temperature units
are set to

degC

. Follow the procedure below to

change this setting. Note that changing the unit here
changes the unit for A30: CAPSULE TEMP (capsule
temperature) and J45: AMP TEMP (amplifier tempera-
ture).

• Example: Change the unit for the temperature

display degC to degF.

ESC

SET
D40:TEMP UNIT
degC
< degC >
< degF >
< K >

Use the or key to

select degF.

Press the key twice to

enter the setting.

F0321.EPS

Then press the (OK) key.

(8) Operation Mode Setup

(D22: REV OUTPUT)

This parameter allows the direction of the 4-20 mA
output to be reversed with respect to input. Follow the
procedure below to make this change.

• Example: Change 4 to 20 mA output to 20 to

4 mA output.

ESC

SET
D22:REV OUTPUT
NORMAL
< NORMAL >
< REVERSE>

Use the or key

to select REVERSE.

Press the key twice to

enter the setting.

F0322.EPS

Then press the (OK) key.

(9) Impulse Line Connection Orientation

Setup (D15: H/L SWAP)

This function reverses the impulse line orientation.
Follow the procedure below to make this change.

• Example: Assign the high pressure impulse

line connection to the L side of
the transmitter.

ESC

SET
D15:H/L SWAP
NORMAL
< NORMAL >
< REVERSE>

Use the or key

to select REVERSE.

Press the key twice to

enter the setting.

F0323.EPS

Then press the (OK) key.

(10) CPU Failure Burnout Direction and Hard-

ware Write Protect (D25: BURNOUT)

There are two slide switches on the CPU assembly
board. One sets the burnout direction at CPU failure,
and the other sets a write protection function which
disables parameter changes through the use of a
handheld terminal or some other communication
method.

HIGH

LOW

CPU assembly

Slide switch

Burnout direction switch

Write protection switch

Write Protection

Switch Position

Burnout Direction

Switch Position

BO H

L

WR E

D

H

L

E

D

H

L

E

D

H

L

E

D

H

L

E

D

Hardware write protection switch (WR)

Burnout direction switch (BO)

Burnout Direction

Write Protection

YES

(Write disabled)

NO

(Write enabled)

F0324.EPS

The parameter of D25: BURNOUT displays the status
of 4-20 mA DC output if a CPU failure occurs. In case
of a failure, communication is disabled.