5. PARAMETER SUMMARY

No.

Parameter name

Item

R/W

Content

Applicable model

Upload

data

F

P

L

Default value

D

AUX SET 1

Auxiliary setting data 1

D35

SP POINT

Decimal place of static pressure

W

0 to 4

D36

SP DAMPING

Damping time constant of SP

W

0.00 to 100.00 sec

D37

SP SELECT

H/L select for static pressure

W

HIGH or LOW

D40

TEMP UNIT

Temperature setting unit

W

degC, degF, or K

D50

QUICK RESP

Quick response

W

OFF or ON (enable 0.00 to 0.50 sec at C30)

D55

WRT PROTECT

Write protect indicator

R

NO or YES

D56

WRT ENABLE

Write protect release

W

8 alphanumeric characters

D57

NEW PASSWORD User set password for write protect

W

8 alphanumeric characters

D58

SOFTWR SEAL

Software seal

R

BREAK or KEEP

D60

SELF CHECK

Self-diagnostics

R

See A60

E

AUX SET 2

Auxiliary setting data 2

E10

T. ZERO CMP

Temperature compensation mode

W

OFF or ON

E11

TEMP ZERO

Zero shift compensation

W

Ϫ

99.999 to 99.999%/degC

E30

BI DIRE MODE

Bidirectional mode

W

OFF or ON

E50

DO SELECT

Contact output select

W

INHIBIT, PRES, SP, TEMP, PRES/SP,
PRES/TEMP, SP/TEMP, or PRES/SP/TEMP

E51

DO SIG. TYPE

Signal type select

W

OFF WHEN ALARM or ON WHEN ALARM

E52

D OUTPUT

Contact output

R

OFF or ON

E60

SELF CHECK

Self-diagnostics

R

See A60

G

ALARM SET

Alarm setting

G10

P AL MODE

Alert mode

W

INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT

G11

P HI. AL VAL

High side alert value

W

Ϫ

32000 to 32000, unit specified in C20

G12

P LO. AL VAL

Low side alert value

W

Ϫ

32000 to 32000, unit specified in C20

G20

SP AL MODE

Static pressure alert mode

W

INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT

G21

SP HI. AL VAL

High side alert value of SP

*

2

W

Ϫ

32000 to 32000, unit specified in D30

G22

SP LO. AL VAL

Low side alert value of SP

W

Ϫ

32000 to 32000, unit specified in D30

G30

T AL MODE

Temperature alert mode

W

INHIBIT, HI. AL DETECT, LO. AL DETECT,
or HI/LO. AL DETECT

G31

T HI. AL VAL

High side alert value of temperature

W

Ϫ

50 to 130

G32

T LO. AL VAL

Low side alert value of temperature

W

Ϫ

50 to 130

G50

AUTO RECOVER Auto-recover from sensor error

W

OFF or ON

G60

SELF CHECK

Self-diagnostics

R

See A60

H AUTO

SET

Automatic

setup

H10

AUTO P LRV

Lower range value auto setup

W

Ϫ

32000 to 32000, unit specified in C20

H11

AUTO P URV

Upper range value auto setup

W

Ϫ

32000 to 32000, unit specified in C20

H20

AUTO SP LRV

SP lower range value auto setup

W

Ϫ

32000 to 32000, unit specified in D30

H21

AUTO SP URV

SP upper range value auto setup

*

2

W

Ϫ

32000 to 32000, unit specified in D30

H60

SELF CHECK

Self-diagnostics

R

See A60

I

DISP SET

Display setting

I10

DISP OUT1

LCD output 1

W

PRES, PRES %, ENGR. PRES, SP, or SP %

I11

DISP OUT2

LCD output 2

W

PRES, PRES %, ENGR. PRES, SP, SP %, or
---

I12

DISP OUT3

LCD output 3

W

See I11

I13

DISP OUT4

LCD output 4

W

See I11

I20

P DISP MODE

% display mode

W

LINEAR or SQUARE ROOT

I21

PRES % RESO

% display resolution

W

NORMAL or HIGH RESOLUTION

I30

ENGR. UNIT

User set engineering unit

W

8 alphanumeric characters

I31

EASY EU SET

Engineering unit select

W

I32 ENGR.

EXP

Exponents

W ---,

ϫ

10,

ϫ

100,

ϫ

1000

I33

ENGR. LRV

User set lower range limit

W

Ϫ

32000 to 32000, unit specified in I30

I34

ENGR. URV

User set upper range limit

W

Ϫ

32000 to 32000, unit specified in I30

I35

ENGR. POINT

Decimal place of user set

W

0 to 4

I40

BAR INDICATR

Bar indicator

W

OFF or ON

I60

SELF CHECK

Self-diagnostics

R

See A60

1

2.00 sec

HIGH

degC

OFF

NO

None

None

KEEP

OFF

0.000%/degC

OFF

INHIBIT

ON WHEN ALARM

OFF

INHIBIT

100.000 kPa

Ϫ

100.000 kPa

INHIBIT

0.00000 MPa

INHIBIT

120 degC

Ϫ

40 degC

ON

As specified

As specified

0.00000 MPa

PRES %

---

---

---

LINEAR

NORMAL

---

0.00

100.00

1

ON

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

*

1: R/W: R = Read only, W = Read & Write

*

2: The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.

*