19) status output (option code al), Example: set the signal characterizer enable – Yokogawa EJX440A User Manual

Page 26

Advertising
background image

IM 01C25T03-01E

3-18

3. OPERATION

F0342.EPS

Y

X

100%

0%

100%

INPUT

OUTPUT

Input pressure in %

Characterized value

• Example: Set the number of coodinates on the

line graph to 5.

ESC

CLR

SET
T11:NUM OF POINT
5

FEED

NO

OK

SET
T11:NUM OF POINT
9
5

F0344.EPS

Set 5.

Press the key twice to

enter the setting.

Press the (OK) key.

• Example: Set the first coordinates (X1, Y1) as

(12, 14) in %.

ESC

CLR

SET
T23:Y1
10.00%
+ 014.00

CLR

ESC

SET
T22:X1
10.00%
+ 012.00

F0345.EPS

PARAM
T21:Y
0.00%
T22:X1
12.00%
T23:Y1
14.00%

PRNT

DATA

DIAG

ESC

Set 12 for X1.

Press the key twice to

enter the setting.

Press the (OK) key.

Set 14 for Y1.

Press the key twice to

enter the setting.

Press the (OK) key.

• Example: Set the signal characterizer ENABLE.

ESC

SET
T10:S.C.ENABLE
ENABLE

FEED

NO

OK

SET
T10:S.C.ENABLE
INHIBIT
< INHIBIT>
< ENABLE >

F0343.EPS

Use the or key

to select ENABLE.

Press the key twice to

activate the function.

Press the (OK) key.

(18)

Process Alarm (G10: P AL MODE, G11: P
HI.AL VAL, G12: P LO.AL.VAL)

The function is used to display the alarm codes when
the input pressure exceeds the specified value within
the calibration range. The same is available for the
input static pressure and the capsule temperature on the
pressure sensor. Refer to table 4.2 Alarm Message
Summary for the specific alarm code to be generated.

• Example: Set alarm mode from OFF to HI.AL

DETECT.

ESC

SET
G10:P AL MODE
HI.AL DETECT

FEED

NO

ESC

SET
G10:P AL MODE
INHIBIT
< INHIBIT >
< HI.AL DETECT >
< LO.AL DETECT >
< HI/LO.AL DETECT >

Use the or key

to select HI. AL DETECT.

Press the key twice to

enter the setting.

Press the (OK) key.

Alarm code is generated when the

output goes beyond the value set

at G11: P HI. AL VAL.

F0346.EPS

• Example: Set the higher alert value of 75 for
alarm generation.

CODE

CAPS

CLR

ESC

SET
G11:P HI.AL VAL
75.0000 kPa

FEED

NO

OK

SET
G11:P HI.AL VAL
100.000 kPa
+ 75

Set 75.

Press the key twice to

enter the setting.

Press the (OK) key.

Then the alarm code “AL.35 P. HI”

is generated when the input

pressure goes beyond that value.

F0347.EPS

(19)

Status Output (option code AL)

This feature is used for a transistor output (open
collector) of an on/off signal according to the status of
high and low alarm limits, which are user-configurable
values as shown in (18) Process Alarm. The status
output can be assigned as any combination of the high
or low limits of the input pressure, input static pres-
sure, or capsule temperature.

CAUTION

Execute DO testing by the parameter "K40 DO
test" whenever turning on the transmitter or
detecting the short interruption in order to check
that the alarm contact output is correctly config-
ured.