4. SELF-DIAGNOSTICS

4.2 Alarms and Countermeasures

Table 4.2 Alarm Message Summary

Indicator

BT200 display

Cause

Countermeasure

Output operation

during error

None

GOOD

AL. 01
CAP. ERR

01: P-SENSOR ERR

AL. 02
AMP. ERR

02: AT-SENSOR ERR

AL. 11
ST. PRSS

11: SP OVER SPEC

AL. 12
CAP. TMP

12: CT OVER SPEC

AL. 13
AMP. TMP

13: AT OVER SPEC

AL. 30
RANGE

30: P OVER RANGE

AL. 35
P. HI

35: P HIGH ALARM

AL. 36
P. LO

36: P LOW ALARM

AL. 37
SP. HI

37: SP HIGH ALARM

AL. 38
SP. LO

38: SP LOW ALARM

AL. 39
TMP. HI

39: CT HIGH ALARM

AL. 40
TMP. LO

40: CT LOW ALARM

AL. 51
P. URV

51: P ILLEG URV

AL. 52
P. SPN

52: P ILLEG SPAN

AL. 53
P. ADJ

53: P SPAN ADJ

53: P ZERO ADJ

AL. 54
SP. RNG

54: SP ILLEG LRV

54: SP ILLEG URV

54: SP ILLEG SPAN

AL. 55
SP. ADJ

55: SP SPAN ADJ

AL. 60
SC. CFG

60: SC CONFIG ERR

55: SP ZERO ADJ

Static pressure exceeds
limit.

Capsule temperature is outside
range (–50 to 130

°

C).

Amplifier temperature is outside
range (–50 to 95

°

C).

Output is outside upper or lower
range limit value.

AL. 31
SP. RNG

31: SP OVER RANGE Static pressure exceeds

specified range.

Input pressure exceeds specified
threshold.

Input static pressure exceeds
specified threshold.

Detected temperature exceeds
specified threshold.

AL. 50
P. LRV

50: P ILLEG LRV

Specified value is outside of
setting range.

Specified values or settings do
not meet the conditions.

T0401.EPS

Sensor problem.

01: CT-SENSOR ERR

Capsule temperature sensor
problem.

01: C-EEPROM ERR

Capsule EEPROM problem.

Amplifier temperature sensor
problem.

02: A-EEPROM ERR

Amplifier EEPROM problem.

02: CPU BOARD ERR Amplifier problem.

Continues to operate and
output.

Continues to operate and
output.

Continues to operate and
output.

Continues to operate and
output holding static
pressure in %.

Outputs the signal (Hi or Low)
set with parameter D26.
[Status output: undefined]

Use heat insulation or
make lagging to keep
temperature within
range.

Check input and range
setting, and change
them as needed.

Check input.

Adjust settings and
change them as needed.

Adjust settings and
change them as needed.

Check settings and change
them as needed.

Check settings and change
them as needed.

AL. 79
OV. DISP

Displayed value exceeds
limit.

Check settings and change
them as needed.

Replace capsule when
error keep appearing error
even after restart.

Replace capsule.

Replace amplifier.

AL. 10
PRESS

10: P OVER SPEC

Input is outside measurement
range limit of capsule.

Outputs upper range limit (URL)
or lower range limit (LRL).

Outputs upper range value
(URV) or lower range value
(LRV).

Continues to operate and
output.

Holds output immediately
before error occurred.

Check input or replace
capsule when necessary.

Check capsule
temperature.

Continues to operate and
output without signal
characterizing.

Continues to operate and
output.