Parameter summary, Parameter summary -1 – Yokogawa EJX440A User Manual

Page 33

Advertising
background image

IM 01C25T03-01E

5-1

5. PARAMETER SUMMARY

5.

PARAMETER SUMMARY

Instruments to which applicable:
F: Differential pressure transmitters
P: Absolute and gauge pressure transmitters
L: Flange mounted differential pressure transmitters

No.

Parameter name

Item

R/W

Content

Applicable model

Upload

data

F

P

L

Default value

01 MODEL

Model

R

02

TAG No.

Tag number

R

03 SELF

CHECK Self-diagnostics

R

A

DISPLAY

Measured data display

A10

OUTPUT

Output (in %)

R

Ϫ

2.5 to 110%

A11

PRES

Measured pressure after zero

R

Unit specified in C20

adjustment

A15

OUTPUT mA

Output current

R

3.6000 to 21.600 mA

A16

ENGR. OUTPUT User scaled value

R

Unit specified in I30

A17

ENGR. EXP

Exponents

R

Unit specified in I32

A20

SP %

Static pressure (in %)

R

Ϫ

10 to 110%

A21

SP

Static pressure after zero

R

Unit specified in D30

adjustment

A30

CAPSULE TEMP Capsule temperature

R

Unit specified in D40

A60

SELF CHECK

Self-diagnostics

R

Refer to Table 4.2 Alarm Message Summary

B

SENSOR TYPE

Sensor type

B10

MODEL

Model and capsule type

R

Model and capsule type

B11

STYLE NO.

Style number

R

Style number of product

B20

PRES LRL

Lower range limit

R

Unit specified in C20

B21

PRES URL

Upper range limit

R

Unit specified in C20

B22

P MIN SPAN

Minimum span

R

Unit specified in C20

B30

SP LRL

Lower range limit for static pressure

R

Unit specified in D30

B31

SP URL

Upper range limit for static pressure

R

Unit specified in D30

B32

SP MIN SPAN

Minimum span for static pressure

R

Unit specified in D30

B60

SELF CHECK

Self-diagnostics

R

See A60

C

BASIC SETUP

Setting data

C10

TAG NO.

Tag number

W

16 alphanumeric characters

C20

PRES UNIT

Measurement range unit

W

mmH2O, mmAq, mmWG, mmHg, Torr, kPa,
MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O,
inHg, ftH2O, psi, atm, Pa, hPa

C21

PRES LRV

Lower range value

W

Ϫ

32000 to 32000 within measurement range

C22

PRES URV

Upper range value

W

Ϫ

32000 to 32000 within measurement range

C23

PRES POINT

Decimal place

W

0 to 4

C30

AMP DAMPING

Damping time constant at amplifier

W

0.50 (0.00) to 100.00 sec, see D50

C40

OUTPUT MODE Output mode

W

LINEAR or SUQARE ROOT

C60

SELF CHECK

Self-diagnostics

R

See A60

D

AUX SET 1

Auxiliary setting data 1

D10

LOW CUT

Low cut

W

0.00 to 20.00%

D11

LOW CUT MODE Low cut mode

W

LINEAR or ZERO

D15

H/L SWAP

Impulse piping accessing direction

W

NORMAL or REVERSE

D16

H2O UNIT SEL

H2O unit select

W

@4degC or @20degC (68.0F)

D20

OUT LIMIT (L)

Low side output limiter

W

Ϫ

2.50 to 110.00%

D21

OUT LIMIT (H)

High side output limiter

W

Ϫ

2.50 to 110.00%

D22

REV OUTPUT

Output reversal

W

NORMAL or REVERSE

D25

BURNOUT

CPU error

R

HIGH or LOW

D26

ERROR OUT

Hardware error

W

BURNOUT DIR or HOLD

D30

SP UNIT

Static pressure unit

W

See C20

D31

SP A/G SLCT

Gauge/Abs select for static pressure

W

GAUGE or ABSOLUTE

D32

ATM. PRESS

Coefficient for given gauge pressure

W

Unit specified in D30

D33

SP LRV

Lower limit of static pressure

W

Ϫ

32000 to 32000 within measurement range

D34

SP URV

Upper limit of static pressure

*

2

W

Ϫ

32000 to 32000 within measurement range

EJX

As specified

GOOD

As specified

kPa

As specified

As specified

2

2.00 sec or as specified

LINEAR or as specified

10.00%

LINEAR

NORMAL

@4degC

Ϫ

2.50%

110%

NORMAL

BURNOUT DIR

MPa

ABSOLUTE

0.10133 MPa

0.0 MPa

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

*

1: R/W: R = Read only, W = Read & Write

*

2: The default value shows MWP (Maximum working pressure) of the capsule.

Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.

*