For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

1.2 Measurng Input Secton

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

• Delta Computaton

The value obtained by subtracting the measured value of another channel (called

the reference channel) from the input value of the channel set to delta computation is
used as the measured value of that channel. The reference channel must be assigned
to a channel whose channel number is less than that of the channel on which delta
computation is specified. The channel on which delta computation is specified is
automatically set to the same range type as the reference channel.

Input

value

Measured value on the reference channel

Channel set to delta computation

Measured value

Note

A channel whose input type is set to DC voltage, TC, or RTD can be designated as a reference
channel. However, channels set to scaling or square root computation cannot be designated.

• Scalng

The input values are scaled to values in the appropriate unit to be used as measured

values.

0 V

–100.0°C

10 V

300.0°C

Measured value

Input value

• Square Root Computaton

When the input type is DC voltage, the square root of the input value is calculated, the

result is scaled to a value in the appropriate unit, and used as the measured value of
the channel. Also, the low-cut function (input less than a given measured value is fixed
to 0% (scale left value)) can be used.

Input value

Input value

Low-cut value

Result of square

root computation

Measured value

Channel set to square root computation

Measured value

Scaling

Note

The square root computation on the recorder uses the following formula.

F = ( F - F )

V - V

V - V

+ F

x

x

max

max

min

min

min

min

where Vmin (leftmost value of span) < Vmax (rightmost value of span)
Fmin (leftmost value of scale after scaling) < Fmax (rightmost value of scale after

scaling)
Vx is the input voltage and Fx is the scaled value

<Related Topcs> Setting the input range: Section 5.1