Yokogawa µR20000 User Manual

Page 26

Advertising
background image

IM 04P02B01-01E

For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

1-10

1.3 Alarms

Reflash Alarm

When multiple alarms are assigned to one alarm output relay, this function notifies the
occurrence of subsequent alarms after the relay is activated by the first alarm. When
subsequent alarms occur, the output relay is released temporarily (approximately
500 ms).
The reflash alarm function is set to three output relays (I01, I02, and I03 (I01 and I02 for
the /A1 option)).
By default, the reflash alarm is disabled.

Alarm

Alarm output relay

(Reflash alarm ON)

Alarm output relay

(Reflash alarm OFF)

Channel 1

Channel 3

Channel 2

Approx. 500 ms Approx. 500 ms

Note

• If the reflash alarm is enabled, I01 to I03 are set to reflash alarm operation. In this case, I01

to I03 are set to OR operation and non-hold operation regardless of the settings specified in
“AND/OR Operation of Alarm Output Relays” and “Non-Hold/Hold Operation of Alarm Output
Relays” described below.

• If diagnosis output is enabled, I01 is set to diagnosis output.

<Related Topcs> Setting the reflash alarm: Section 7.1

Advertising