16. When Voc and Isc measurements are complete, the

message “OK” is shown in case the result of the test is
positive (measured values within the tolerances set on the
instrument)

17. With insulation measurement selected, the instrument

goes on with the test keeping terminals P and N short-
circuited, and carrying out the test between this point and
terminal E for the time necessary to obtain a steady value.

18. The value of insulation resistance is shown in field “Ri” and

the message “OK” appears in case the result of the test is
positive (measured value higher than the minimum limit
value set on the instrument).

15/05/12 15:34:26

M o d u l e :

S U N P W R 3 1 8

V d c :

5 4 8 . 0 V

I r r

:

8 5 6 W / m 2

T c :

A u t o

° C

V o c , I s c :

O K

R i ( 1 0 0 0 V ) 1 1 6 M

 O K

R p e ( C a l )

- - -

Measuring…

Selection

I V C K

19. With continuity measurement selected, the instrument

goes on by opening the short-circuit and carrying out the
test between terminals E and C.

20. The value of resistance in the continuity test is shown in

field “Rpe” and the message “OK” appears in case the
result of the test is positive (measured value lower than
the maximum limit value set on the instrument).

21. The message “Outcome:OK” is finally shown by the

instrument in case the result of all performed tests is
positive.

15/05/12 15:34:26

M o d u l e :

S U N P W R 3 1 8

V d c :

5 4 8 . 0

V

I r r

:

8 5 6 W / m 2

T c :

A u t o

° C

V o c , I s c :

O K

R i ( 1 0 0 0 V ) 1 1 6 M

 O K

R p e ( C a l )

2 . 0 0

 O K

Outcome: OK

I V C K

22. Press the arrow key

 to show the following page in

which the values of parameters Voc and Isc are shown. It
shows:

 The module being used
 The value of irradiance
 The value of temperature of the module
 The average values of Voc and Isc under OPC
 The values of Voc and Isc measured under OPC

 The values of Voc and Isc calculated under STC and

the relevant partial results obtained by comparison with
the nominal values.

In general:

15/05/12 15:34:26

M o d u l e : S U N P W R 2 1 0
I r r

- - - W / m 2

T c ( A U T O )

5 7 ° C

V o c A v g @ O P C

6 4 7

V

I s c A v g @ O P C

5 . 4 3

A

V o c @ O P C

6 4 7

V

I s c @ O P C

5 . 3 5

A

V o c @ S T C

7 8 7

V O K

I s c @ S T C

5 . 7 2

A O K

Outcome: OK

I V C K

4%

Isc

Tol

100

se

4%

Voc

Tol

100

se

@

@

@

@

@

@

@

@

STC

STC

STC

STC

STC

STC

STC

STC

IscNom

Isc

IscNom

OK

Isc

Esito

VocNom

Voc

VocNom

OK

Voc

Esito

The rated values of Voc and Isc are the values found in the instrument’s internal
modules’ DB (see § 5.6).

 The overall value of the results: