6.5.3.1. Anomalous
situations
1. In case the instrument detects a voltage higher than 5V at
its terminals E and C, it does not carry out the test, gives
out a long sound and displays the message “Voltage >
Lim”.
15/05/12 15:34:26
R P E m a x
:
1
R c a l
:
- - -
R p e
=
- - -
I t e s t
=
- - -
m A
V o l t a g e > L i m
Selection
L O W
2. In case the instrument detects that the calibrated
resistance is higher that the measured resistance, the
instrument gives out a long sound and displays the
message: “Calibration not OK”
15/05/12 15:34:26
R P E m a x
:
1
R c a l
:
- - -
R p e
=
- - -
I t e s t
=
- - -
m A
C a l i b r a t i o n n o t O K
Selection
L O W
3. In case the instrument detects a resistance higher than
5
at its terminals, it gives out a long sound, zeroes the
compensated value and displays the message
“Calibration reset”.
15/05/12 15:34:26
R P E m a x
:
1
R c a l :
0 . 0 0
R p e
=
- - -
I t e s t
=
- - -
m A
C a l i b r a t i o n r e s e t
Selection
L O W