Caution, Pvcheck – HT instruments PVCHECK User Manual

Page 43

Advertising
background image

PVCHECK

EN - 41

6.4.3. Measuring insulation – TIMER mode
1. Position the cursor onto M

 by using the arrow keys

(

,) and confirm with ENTER. The display shows the

screen to the side.

2. Press the ENTER key, activate “Settings” and possibly

change the desired parameters (see § 5.4). The following
parameters are shown on the display:

Ins. Test  selected test voltage (250, 500 or

1000VDC)

Ri min  minimum limit threshold for insulation

measurement

Mode  measuring mode: TIMER
Vtest  real applied test voltage
Ri (+)  minimum insulation resistance between the

Positive pole and the earthing detected during the
whole duration of measurement.

Test time  test duration which can be set within a

range of 10

300s

  key  access to the second page with the

measured values of VPN, VEP and VEN voltages

15/05/12 15:34:26

I n s . T e s t

:

1 0 0 0

V

R i m i n

:

1 . 0

M

M o d e :

T i m e r

V t e s t

- - -

V

R i ( + )

- - -

M

T e s t t i m e : 1 0 s

Selection

M

3. Connect the instrument to the PV module/string being tested and then to possible

unearthed metal masses and to the main earth node of the system (see Fig. 11). In
particular, connect the positive output pole of the PV module/string and the metal
masses to terminal P.

CAPTION:

E: Green

cable

P: Red

cable

N: Black cable

1. Unearthed PV

module/string

2. Main

system

earthing

3. Massa metallica

non collegata a
terraUnearthed
metal mass

Fig. 11: Instrument connection for insulation measurement in TIMER mode

CAUTION

Upon pressing the GO/STOP key, different error messages can be displayed
by the instrument (see § 6.6) and, therefore, the test cannot be started. Check
and eliminate, if possible, the problem causing the error message before going
on with the test.