11. APPENDIX – THEORETICAL OUTLINE

11.1. EFFICIENCY TEST ON PV INSTALLATIONS
According to the requirements of the laws in force, DC efficiency test on a PV installation
depends on the type of correction used to compensate the effects of the module’s
temperature and on the mathematical relationship used to calculate the nDC parameter
(see § 5.2.3).

Corr. Tcel

value

Mathematical relationship for nDC

calculation

Standar

d

Result

Tmod

Tcel = Measured module temp.

value



C)

40

Tcel

(se

100

40)

-

(Tcel

-

1

C)

40

Tcel

(se

1

fv2

R

hence

n

STC

p

dc

P

G

G

Rfv

P

nDC

2

Italian

guideline

CEI

82-25

OK/NO

Tenv

Tcel = Calculated module temp.

value

800

G

20

Tamb

Tcel

p

NOCT

nDC

Tcel = Measured module temp.

value

n

dc

cel

p

STC

P

P

T

G

G

nDC

25

100

1

- - -

- - -

where:

Symbol Description

Measurin

g unit

p

G

Irradiance measured on PV module surface

2

W/m

STC

G

Standard Irradiance = 1000

2

W/m

n

P

Rated Power = sum of all Pmax values of the section of the PV plant being
measured

 

kW

dc

P

DC power measured at the PV generator’s output

 

kW

2

Rfv

Correction factor depending on the Temperature of PV Cells (Tcel) measured or
calculated according to the type of selected correction relationship

Absolute value of the thermal coefficient of Pmax of the PV modules included in the
plant section being measured.

C

%/

NOCT

(Normal Operating Cell Temperature) = Temperature the cells under reference
conditions are brought to (800W/m

2

, 20°C, AM=1.5, air speed =1m/s).

C

%/

The previous relationships are valid if Irradiance > Min Irradiance (see the User Manual of the MASTER
instrument) and the irradiance values are “steady”, i.e. for each sample taken, with IP

1min, the

difference between the maximum and minimum irradiance values measured must be < 20W/m

2

The final OUTCOME can be:

Non-displayable: if the obtained values are inconsistent (e.g. nDC >1.15) or if

irradiation has never reached a steady value > minimum threshold set.

 The maximum performance of the system

The highest performance (maximum value of nDC) is detected according with previous
relationships